Fire performance evaluation of cladding wall assemblies using the 16-ft high parallel panel test method of ANSI/FM 4880

被引:11
作者
Agarwal, Gaurav [1 ]
Wang, Yi [1 ]
Dorofeev, Sergey [1 ]
机构
[1] FM Global, Fire Hazards & Protect, Div Res, 1151 Boston Providence Turnpike, Norwood, MA 02062 USA
关键词
aluminum composite materials (ACMs); FM; 4880; BS; 8414; cladding assemblies; facade fire; high-pressure laminates (HPLs); NFPA; 285; DIFFERENTIATION;
D O I
10.1002/fam.2852
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Cladding assemblies are facade systems made of cladding panels such as aluminum composite materials (ACMs) and high-pressure laminates (HPLs), and layers of continuous insulation (CI) and weather resistive barrier (WRB). Recent incidents of catastrophic fires involving cladding assemblies have warranted efforts to understand their fire hazards and develop engineering risk mitigation guidelines for existing constructions. This research provides a comprehensive fire performance evaluation of cladding assemblies exposed to realistic fire scenarios. Twelve cladding assemblies, with a combination of four types of claddings, four types of CIs, and two WRBs are selected. The tests are conducted using the 16-ft (4.9 m) high parallel panel test (16-ft PPT) method of ANSI/FM 4880 standard; the method imparts realistic >100 kW/m( 2 ) heat flux to the wall assemblies. The results show that the chemical heat release rate (HRR) based evaluation criterion used in the 16-ft PPT provides an objective and robust assessment of fire performance. The wall assemblies comprising of thermoplastic-core ACMs demonstrated accelerated flame spread within a matter of a few minutes, regardless of the combustibility of the CI used. At low heat flux exposures, unlike severe fire scenarios of the 16-ft PPT, it is shown that the thermoplastic-core ACMs appear to perform favorably. The fire-retardant ACM and HPL assemblies reveal limited flame spread, regardless of whether the CI used in the assembly was charring combustible or noncombustible. Lastly, for the assemblies evaluated, the flammability of claddings exhibits greater influence on the overall performance of the wall system, while the CI and WRB affect the system performance in a secondary manner.
引用
收藏
页码:609 / 623
页数:15
相关论文
共 53 条
[1]  
Agarwal G., 2017, 4880 ANSIFM
[2]  
Agarwal G, 2018, 12 SFPE INT C PERF B
[3]  
Alpert R.L., 2003, Fire Saf. Sci, V7, P41, DOI [10.3801/IAFSS.FSS.7-41, DOI 10.3801/IAFSS.FSS.7-41]
[4]  
Alpert RL, 2002, J FIRE PROT ENG, V12, P245
[5]  
American National Standard for Evaluating the Fire Performance of Insulated Building Panel Assemblies and Interior Finish Materials, 2017, 48802017 ANSIFM AM N
[6]   Modeling of fire exposure in facade fire testing [J].
Anderson, J. ;
Bostroem, L. ;
McNamee, R. Jansson ;
Milovanovic, B. .
FIRE AND MATERIALS, 2018, 42 (05) :475-483
[7]  
[Anonymous], 2017, 8414 DCLG BS BRE GLO
[8]  
[Anonymous], 2015, CHARLTON WAREHOUSE F
[9]  
[Anonymous], 2017, LONDON FIRE VISUAL G
[10]  
[Anonymous], 2017, SHOULD KNOWSLEY HEIG