A CO2/O2 Mixed Gas DC Circuit Breaker With Superconducting Fault Current-Limiting Technology

被引:29
作者
Xiang, Bin [1 ]
Gao, Lei [1 ]
Luo, Jinhui [1 ]
Wang, Chuanchuan [2 ]
Nan, Zhenle [2 ]
Liu, Zhiyuan [1 ]
Geng, Yingsan [1 ]
Wang, Jianhua [1 ]
Yanabu, Satoru [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Dept Elect Engn, Xian 710049, Peoples R China
[2] High Voltage Apparat Co Ltd, Xian 710018, Peoples R China
基金
中国博士后科学基金; 中国国家自然科学基金;
关键词
Sulfur hexafluoride; Circuit breakers; Fault currents; Power system reliability; Superconducting coils; Gases; Superconducting transmission lines; CO2; O2 gas circuit breaker; DC interruption; mixed CO2; O2; gases; passive resonance; superconducting fault current-limiting technology;
D O I
10.1109/TPWRD.2019.2957499
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Researchers have investigated the interruption properties of CO2 gas, including CO2 and O-2 mixed gas. However, there has been no research on the passive resonance DC interrupting characteristics of CO2/O-2 mixed gas. The objective of this paper is to learn the passive resonance DC interrupting properties of CO2/O-2 mixed gas with superconducting fault current-limiting technology. A proposed passive resonance DCCB that includes a superconducting current-limiting module (SCLM) and a DC interrupting module (DCIM) connected in series was tested for DC voltages of 1.3, 3 and 10 kV and DC currents from 50 A to 10 kA. The experimental results show that the DCCB could successfully interrupt a 10 kA current in a 10 kV DC system. The response time of the DCCB was only 0.3 ms. After interruption, there was no overvoltage. The arcing time and the arc voltage of the SF6 gas and the CO2/O-2 mixed gas were also compared experimentally. Experimental results show that CO2/O-2 mixed gas may be a good substitute for the SF6 gas in passive resonance interruption. The CO2/O-2 mixed gas passive resonance DCCB combined with the SCLM is an effective way to interrupt high short-circuit fault currents in medium-voltage and high-voltage DC systems.
引用
收藏
页码:1960 / 1967
页数:8
相关论文
共 26 条
  • [1] High-Wire Act
    Adapa, Ram
    [J]. IEEE POWER & ENERGY MAGAZINE, 2012, 10 (06): : 18 - 29
  • [2] [Anonymous], THESIS
  • [3] On the Performance of Widely Linear SC-FDE Systems for Underwater Acoustic Communication
    Chang, Bruno S.
    Souza, Richard D.
    Pellenz, Marcelo E.
    [J]. OCEANS 2015 - GENOVA, 2015,
  • [4] Chen ZX, 2015, 2015 3RD INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST), P36, DOI 10.1109/ICEPE-ST.2015.7368390
  • [5] [郭晓雪 Guo Xiaoxue], 2014, [高电压技术, High Voltage Engineering], V40, P3085
  • [6] Junaid M., 2019, IEEE T APPL SUPERCON, V29, P1
  • [7] Knobloch H., 1998, Gaseous Dielectrics VIII, P565
  • [8] Impact of SFCL on the Four Types of HVDC Circuit Breakers by Simulation
    Lee, Jong-Geon
    Khan, Umer Amir
    Lee, Ho-Yun
    Lee, Bang-Wook
    [J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2016, 26 (04)
  • [9] Studies on the Application of R-SFCL in the VSC-Based DC Distribution System
    Li, Bin
    He, Jiawei
    [J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2016, 26 (03)
  • [10] LI MY, 2014, CHIN J SHIP RES, V9, DOI DOI 10.1186/1749-8090-9-118