Spatio-temporal distribution of gaseous pollutants from multiple sources in industrial buildings with different flow patterns

被引:7
作者
Cao, Yingxue [1 ,2 ]
Wang, Yi [2 ,3 ]
Yu, Zhuolei [3 ]
Lu, Caiwu [1 ]
Wu, Songheng [2 ,3 ]
Yang, Yang [3 ]
Meng, Xiaojing [1 ]
机构
[1] Xian Univ Architecture & Technol, Sch Resources Engn, 13 Yanta RD, Xian 710055, Shaanxi, Peoples R China
[2] Xian Univ Architecture & Technol, State Key Lab Green Bldg Western China, Xian, Shaanxi, Peoples R China
[3] Xian Univ Architecture & Technol, Sch Bldg Serv Sci & Engn, 13 Yanta RD, Xian 710055, Shaanxi, Peoples R China
关键词
multiple time-series sources; flow pattern; long and narrow industrial building; industrial ventilation; gaseous pollutants; UNBOUNDED STRATIFIED FLOWS; TURBULENT BUOYANT JETS; AIR-FLOW; EXHAUST VENTILATION; INTEGRAL MODEL; TRACER-GASES; ROOM AIR; ACCURACY; REMOVAL; SYSTEMS;
D O I
10.1007/s12273-022-0886-z
中图分类号
O414.1 [热力学];
学科分类号
摘要
Energy consumption of industrial buildings has remained continuously high, and the environmental quality requirements are also constantly improving. Only by improving industrial environmental control technology based on the transport mechanism of the pollution, can the energy consumption of industrial building environmental control be further reduced, and the environmental quality of industrial buildings can be improved as well. Therefore, after verifying the numerical simulation by experiments, this study uses a self-label method to investigate the spatio-temporal distribution of gaseous pollutants from multiple time-series sources in industrial plants with different length-span ratios. The results show that, the polluted flow in plants with different aspect ratios have different flow patterns: (i) the "Back-mixing" flow pattern occurs when the ratio of ventilation rate G and polluted flow rate at the exhaust height L-P is less than 1, i.e., G/L-P < 1, and (ii) the "One-way" flow pattern occurs when G/L-P > 1. For plants with the "Back-mixing" pattern, the following source pollutants enter a density stratified environment induced by the retained pre-source pollutants. The flow of following source pollutants released at the same intensity as the precursor source can reach the roof, while those with low velocity and density difference may be blocked during the ascending process. The maximum height z(m) of the flow of the following source is related to both the initial Froude number Fr-0 of the following source and the unsteady vertical density gradient of the fluid in the indoor environment d rho(a)/dz. For plants with the "One-way" pattern, the flow from the following source enters into an environment with approximately uniform density. Under the condition of positive buoyancy, design parameters of ventilation corresponding to the vicinity of G/L-P = 1 may be the optimal solution for safety and energy conservation.
引用
收藏
页码:1629 / 1644
页数:16
相关论文
共 61 条
  • [1] ACGIH HA, 2019, IND VENT MAN REC PRA
  • [2] Anderson JD., 2006, HYPERSONOC HIGH TEMP
  • [3] Modeling Detached Flows at the Inlet to Round Suction Flues With Annular Screens
    Averkova, O. A.
    Logachev, I. N.
    Logachev, K. I.
    Khodakov, I. V.
    [J]. REFRACTORIES AND INDUSTRIAL CERAMICS, 2014, 54 (05) : 425 - 429
  • [4] Batchelor C. K., 2000, CHROMOPHOBIA
  • [5] Baturin V., 1972, Fundamentals of industrial ventilation
  • [6] Bird R. B., 2007, TRANSPORT PHENOMENA, V2nd ed.
  • [7] Evaluation of a novel curved vortex exhaust system for pollutant removal
    Cao, Zhixiang
    Zhang, Chen
    Zhai, Chao
    Wang, Yi
    Wang, Meng
    Zhao, Tongtong
    Lv, Wenchao
    Huang, Yanqiu
    [J]. BUILDING AND ENVIRONMENT, 2021, 200
  • [8] Performance evaluation of different air distribution systems for removal of concentrated emission contaminants by using vortex flow ventilation system
    Cao, Zhixiang
    Wang, Yi
    Zhai, Chao
    Wang, Meng
    [J]. BUILDING AND ENVIRONMENT, 2018, 142 : 211 - 220
  • [9] Study of the vortex principle for improving the efficiency of an exhaust ventilation system
    Cao, Zhixiang
    Wang, Yi
    Duan, Mengjie
    Zhu, Huaxin
    [J]. ENERGY AND BUILDINGS, 2017, 142 : 39 - 48
  • [10] COMPARISON OF DIFFERENT K-EPSILON MODELS FOR INDOOR AIR-FLOW COMPUTATIONS
    CHEN, Q
    [J]. NUMERICAL HEAT TRANSFER PART B-FUNDAMENTALS, 1995, 28 (03) : 353 - 369