Sliding Mode Control with Fixed Switching Frequency for Four-wire Shunt Active Filter

被引:6
作者
Hamoudi, Farid [1 ]
Chaghi, A. Aziz [2 ]
Amimeur, Hocine [3 ]
Merabet, El Kheir [3 ]
机构
[1] Boumerdes Univ, Inst Elect & Elect Engn, Boumerdes, Algeria
[2] Batna Univ, LSPIE Lab, Batna, Algeria
[3] Batna Univ, Dept Elect Engn, Batna, Algeria
关键词
Sliding mode control; Switching frequency; Four-wire active filter; Current harmonics compensation; POWER FILTER; REACTIVE POWER; 3-PHASE;
D O I
10.5370/JEET.2011.6.5.647
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The present paper proposes a sliding mode control with fixed switching frequency for three-phase three-leg voltage source inverter based four-wire shunt active power filter. The aim is to improve phase current waveform, neutral current mitigation, and reactive power compensation in electric power distribution system. The performed sliding mode for active filter current control is formulated using elementary differential geometry. The discrete control vector is deduced from the sliding surface accessibility using the Lyapunov stability. The problem of the switching frequency is addressed by considering hysteresis comparators for the switched signals generation. Through this method, a variable hysteresis band has been established as a function of the sliding mode equivalent control and a predefined switching frequency in order to keep this band constant. The proposed control has been verified with computer simulation which showed satisfactory results.
引用
收藏
页码:647 / 657
页数:11
相关论文
共 32 条
[1]  
Akagi H., 1983, IPEC-Tokyo Conference Record of the International Power Electronics Conference 1983, P1375
[2]  
[Anonymous], 1999, Sliding mode control in electromechanical systems
[3]  
[Anonymous], 2004, THESIS LAPPEENRANTA
[4]   Three-phase four-wire shunt active filter control strategies [J].
Aredes, M ;
Hafner, J ;
Heumann, K .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1997, 12 (02) :311-318
[5]   NEW CONTROL ALGORITHMS FOR SERIES AND SHUNT 3-PHASE 4-WIRE ACTIVE POWER FILTERS [J].
AREDES, M ;
WATANABE, EH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (03) :1649-1656
[6]   New control approach for four-wire active power filter based on the use of synchronous reference frame [J].
Benhabib, MC ;
Saadate, S .
ELECTRIC POWER SYSTEMS RESEARCH, 2005, 73 (03) :353-362
[7]  
BOROYEVICH D, 2002, IEEE T POWER ELECT, V17
[8]   AN ADAPTIVE HYSTERESIS-BAND CURRENT CONTROL TECHNIQUE OF A VOLTAGE-FED PWM INVERTER FOR MACHINE DRIVE SYSTEM [J].
BOSE, BK .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1990, 37 (05) :402-408
[9]  
Buhler H., 1986, REGLAGE MODE GLISSEM
[10]   Comparison of current control techniques for active filter applications [J].
Buso, S ;
Malesani, L ;
Mattavelli, P .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1998, 45 (05) :722-729