Risk evaluation of combinative transmission network and substation configurations and its application in substation planning

被引:23
作者
Li, WY [1 ]
Lu, JP
机构
[1] British Columbia Transmission Corp, Syst Planning & Performance Assessment, Vancouver, BC V7X 1V5, Canada
[2] Chongqing Univ, Coll Elect Engn, Chongqing 40004, Peoples R China
关键词
composite system reliability; probabilistic economic analysis; substation planning; substation reliability; system risk assessment;
D O I
10.1109/TPWRS.2005.846112
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a method to perform risk assessment of a combinative system of transmission network and substation configurations. Compared to the traditional approach, in which system risks of transmission networks and substation configurations are separately assessed, the presented method can automatically capture the mutual impacts between the transmission network and substation arrangements. The key of the method is the united load curtailment model for the combinative system. The presented risk evaluation procedure also provides a vehicle to perform the probabilistic economic analysis for system reinforcement schemes. A simple example is offered to demonstrate the risk evaluation of two substation layouts under a transmission network environment and its application to the financial justification of the ring-bus structure vis-a-vis the section-bus structure in the given substation.
引用
收藏
页码:1144 / 1150
页数:7
相关论文
共 17 条
[1]   TERMINAL EFFECTS AND PROTECTION SYSTEM FAILURES IN COMPOSITE SYSTEM RELIABILITY EVALUATION [J].
ALLAN, RN ;
ADRAKTAS, AN .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (12) :4557-4562
[2]   MODELING AND ASSESSMENT OF STATION ORIGINATED OUTAGES FOR COMPOSITE SYSTEMS RELIABILITY EVALUATION [J].
ALLAN, RN ;
OCHOA, JR .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1988, 3 (01) :158-165
[3]   Bibliography on the application of probability methods in power system reliability evaluation - 1992-1996 [J].
Allan, RN ;
Billinton, R ;
Breipohl, AM ;
Grigg, CH .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1999, 14 (01) :51-57
[4]   Individual generating station reliability assessment [J].
Billinton, R ;
Chen, H ;
Zhou, JQ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1999, 14 (04) :1238-1244
[5]   HYBRID APPROACH FOR RELIABILITY EVALUATION OF COMPOSITE GENERATION AND TRANSMISSION-SYSTEMS USING MONTE-CARLO SIMULATION AND ENUMERATION TECHNIQUE [J].
BILLINTON, R ;
WENYUAN, L .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1991, 138 (03) :233-241
[6]   STATION-INITIATED OUTAGES IN COMPOSITE-SYSTEM ADEQUACY EVALUATION [J].
BILLINTON, R ;
VOHRA, PK .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1987, 134 (01) :10-16
[7]   STATION RELIABILITY EVALUATION USING A MONTE-CARLO APPROACH [J].
BILLINTON, R ;
LIAN, G .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) :1239-1245
[8]  
Billinton R., 1984, Reliability Evaluation of Power Systems, DOI DOI 10.1007/978-1-4615-7731-7
[9]  
Billinton R., 1994, Reliability assessment of electrical power systems using Monte Carlo methods
[10]  
CIGRE Task Force 38-03-10, 1991, CIGRE S EL POW SYST