Statistical analysis of non-standard overvoltage waveforms measured at 220 kV terminals of a power transformer
被引:3
|作者:
Jurisic, Bruno
[1
]
Filipovic-Grcic, Bozidar
[2
]
Zupan, Tomislav
[1
]
Levacic, Goran
[3
]
机构:
[1] KONCAR Elect Engn Inst Inc, Zagreb 10002, Croatia
[2] Univ Zagreb, Fac Elect Engn & Comp, Zagreb 10000, Croatia
[3] Croatian Transmiss Syst Operator Ltd, Zagreb 10000, Croatia
关键词:
Non-standard overvoltages;
Lightning;
Power transformer;
Statistical analysis;
Genetic algorithm;
OIL-IMMERSED TRANSFORMERS;
BREAKDOWN CHARACTERISTICS;
INSULATION CHARACTERISTICS;
STANDARD;
D O I:
10.1016/j.epsr.2021.107318
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
Power transformers are designed to withstand switching and lightning overvoltages which can occur in the power system. The knowledge about waveshapes of these events grows rapidly with the introduction of online transient monitoring systems. Consequently, it is important to compare standard test voltage impulses with the ones existing in the power system. In this paper, 123 measured overvoltages in 220 kV air-insulated substation are analyzed. The observed overvoltages are fitted using double exponential mathematical function. Function parameters are calculated using genetic algorithm. To compare measured signals with the standard ones, statistical analysis of their parameters is performed. This approach can help in better dimensioning of the transformer insulation in order to withstand the real overvoltages that can occur in the power network and in avoiding potentially dangerous situation due to the resonances. Additionally, frequency domain severity factor is calculated for the observed signals.
引用
收藏
页数:7
相关论文