Optimal impedance termination of 25-kV electrified railway systems for improved power quality

被引:70
作者
Tan, PC [1 ]
Loh, PC
Holmes, DG
机构
[1] Monash Univ, Dept Elect Comp & Syst Engn, Clayton, Vic 3800, Australia
[2] Nanyang Technol Univ, Ctr Adv Power Elect, S-639798 Singapore, Singapore
基金
澳大利亚研究理事会;
关键词
active power filters; harmonics; power quality; traction systems;
D O I
10.1109/TPWRD.2004.834308
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Many single-phase 25-kV electrified railway systems today are loaded with conventional ac-dc thyristor-based locomotives, which draw current rich in harmonic content. The flow of this harmonic current through the feeder impedance can result in a distorted pantograph voltage waveform, which, in turn, can constrain the amount of power delivered to the locomotives. A possible solution to improve the supply quality is to connect a hybrid power-quality conditioner consisting of active and passive elements at the end of the traction feeder. However, if not appropriately designed, the installation of a power-quality conditioner can result in harmonic amplification at some points along the feeder. This paper now presents an analysis to study how the power-quality conditioner must function to implement an optimal impedance termination at the end of the feeder to achieve uniform harmonic suppression along the whole feeder length. The theoretical concepts presented have been confirmed in simulation and experimentally using a model traction system.