A design methodology for thermal storages in heat pump systems to reduce partial-load losses

被引:4
作者
Conti, Paolo [1 ]
Franco, Alessandro [1 ]
Bartoli, Carlo [1 ]
Testi, Daniele [1 ]
机构
[1] Univ Pisa, Dept Energy Syst Terr & Construct Engn DESTEC, I-56122 Pisa, Italy
关键词
Heat pumps; On; off cycling losses; Design methodology thermal energy storage; Dynamic energy simulation; Hardware-in-the-loop; Hydronics; EFFICIENCY DEGRADATION; CYCLING LOSSES; ENERGY STORAGE; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2022.118971
中图分类号
O414.1 [热力学];
学科分类号
摘要
The paper deals with the sizing and the arrangement of thermal energy storages in heat pump systems for building service. Partial-load losses are an increasingly important phenomenon in high-efficiency buildings, even for inverter heat pumps, due to the low average thermal demand compared to the installed capacity. The paper discusses partial-load losses through the data collected during a "hardware-in-the-loop" experimental campaign. Then, it presents a straightforward methodology that can be practically used by HVAC designers to easily determine the volume and the best arrangement of thermal energy storages in heat pump systems. Shortly, thermal storage in a series configuration is an effective solution to make the compressor work at its maximum performance, provided that the thermal efficiency of the storage is higher than the partial-load penalization coefficient of the heat pump. The proposed design methodology is applied to a test case, consisting of a high -efficiency dwelling: depending on the heat pump control characteristics, the electricity consumption can be reduced up to 45 % using a thermal storage. For standard values of the degradation coefficient (0.75-0.9), the seasonal energy saving is in the range 10-20% with a tank loss coefficient lower than 5 W/K.
引用
收藏
页数:16
相关论文
共 42 条
  • [1] [Anonymous], 2017, 1531642 EN
  • [2] [Anonymous], 2018, EN 14511 2
  • [3] [Anonymous], 2018, EN 14825:2018
  • [4] [Anonymous], 2021, REHVA Journal European heat pump market
  • [5] [Anonymous], 2007, 15450 EN
  • [6] Cycling losses in refrigeration equipment: An experimental evaluation
    Bagarella, Giacomo
    Lazzarin, Renato M.
    Lamanna, Biagio
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (08): : 2111 - 2118
  • [7] Optimal operation, configuration and sizing of generation and storage technologies for residential heat pump systems in the spotlight of self-consumption of photovoltaic electricity
    Beck, T.
    Kondziella, H.
    Huard, G.
    Bruckner, T.
    [J]. APPLIED ENERGY, 2017, 188 : 604 - 619
  • [8] Bo M., 2015, MANUALE AUSILIO PROG
  • [9] Air Source Heat Pumps field studies: A systematic literature review
    Carroll, P.
    Chesser, M.
    Lyons, P.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2020, 134
  • [10] Energy and economic analysis of a building air-conditioner with a phase change material (PCM)
    Chaiyat, Nattaporn