Electric Contact Material Selection for Medium and High Voltage DC Circuit Breakers

被引:10
作者
Damle, Tushar [1 ]
Varenberg, Michael [2 ]
Graber, Lukas [1 ]
机构
[1] Georgia Inst Technol, Sch Elect & Comp Engn, Atlanta, GA 30332 USA
[2] Georgia Inst Technol, Woodruff Sch Mech Engn, Atlanta, GA 30332 USA
基金
美国国家科学基金会;
关键词
Contact materials; Electric contacts; Fast mechanical disconnect switch; Ultra fast disconnector; Hybrid circuit breaker; FRETTING CORROSION; DEGRADATION; CONNECTIONS; RESISTANCE; DESIGN; WEAR;
D O I
10.1007/s42341-020-00180-5
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Medium and high voltage DC grids are increasingly proposed for terrestrial, shipboard and aircraft power systems. However, multi terminal DC networks can only be realized with the development of a DC circuit breaker. Due to the difficulty in breaking DC currents, hybrid circuit breakers-which consist of a non-arcing fast mechanical disconnect switch (FMS) in parallel with a solid state switch-is the most promising solution. The stresses experienced by the electric contacts of FMS are different from those of AC and low voltage DC breakers and disconnect switches. The choice of contact material has a significant impact on the performance of the DC circuit breaker. The Ashby method is used to systematically identify the best suited contact materials by translating the requirements of FMS contacts into objectives and constraints and deriving material indices for each objective. Minimizing power loss, wear and overheating of contacts are identified as the key objectives. The results suggest that copper-based alloys and compounds are more suitable than silver based alloys and compounds and other contact materials.
引用
收藏
页码:329 / 338
页数:10
相关论文
共 43 条
[1]  
Amft D, 1996, ISDEIV - XVIITH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, PROCEEDINGS, VOLS I AND II, P732, DOI 10.1109/DEIV.1996.545458
[2]  
[Anonymous], S FRETT CORR ASTM IN
[3]  
[Anonymous], IEEEStdC37.06-2009(2009), P1, DOI [DOI 10.1109/IEEESTD.2009.5318709, 10.1109/IEEESTD.2009.5318709]
[4]  
[Anonymous], 2011, MAT SELECTION MECH D
[5]   ELECTRICAL EFFECTS OF FRETTING CONNECTOR CONTACT MATERIALS - A REVIEW [J].
ANTLER, M .
WEAR, 1985, 106 (1-3) :5-33
[6]   FIELD STUDIES OF CONTACT MATERIALS - CONTACT RESISTANCE BEHAVIOR OF SOME BASE AND NOBLE-METALS [J].
ANTLER, M .
IEEE TRANSACTIONS ON COMPONENTS HYBRIDS AND MANUFACTURING TECHNOLOGY, 1982, 5 (03) :301-307
[7]  
Behrens V, 1995, ELECTRICAL CONTACTS - 1995: PROCEEDINGS OF THE FORTY-FIRST IEEE HOLM CONFERENCE ON ELECTRICAL CONTACTS, P393, DOI 10.1109/HOLM.1995.482896
[8]   Conduction degradation by fretting corrosion phenomena for contact samples made of high-copper alloys [J].
Beloufa, Amine .
TRIBOLOGY INTERNATIONAL, 2010, 43 (11) :2110-2119
[9]  
Bosworth M, 2017, 2017 IEEE ELECTRIC SHIP TECHNOLOGIES SYMPOSIUM (ESTS), P419, DOI 10.1109/ESTS.2017.8069316
[10]  
Braunovic M., 1998, ICEC '98. 19th International Conference on Electric Contact Phenomena, P283