Comparative assessment of different air-conditioning systems for nearly/net zero-energy buildings

被引:37
作者
Singh, Gaurav [1 ]
Das, Ranjan [1 ]
机构
[1] Indian Inst Technol Ropar, Dept Mech Engn, Ropar 140001, Punjab, India
关键词
biomass; building cooling; cost analysis; net zero-energy building; solar energy; RADIANT COOLING SYSTEM; PERFORMANCE ASSESSMENT; SOLID DESICCANT; ABSORPTION; HOT;
D O I
10.1002/er.5065
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This study deals with the performance of different air-conditioning strategies for achieving the target of nearly/net zero energy in a medium-scale building under various environmental conditions. In particular, vapour compression (VC), vapour absorption (VA), and integration of radiant cooling technology are analysed using renewable energy resources emissions and solar photovoltaic (PV)-based electricity. Four different kinds of air-conditioning configurations are considered: VC-based, VA-based, VC-radiant air-conditioning technology with VC dedicated outdoor air system (DOAS) and VA radiant air-conditioning technology with VC-DOAS. Numerical model validations with the benchmark standards are done for VC- and VA-based systems. In particular, annual electric consumption, electricity generation, thermal load generation among all configurations, emissions and solar fractions are studied. The present study shows that target of nearly/net zero-energy building can be achieved in an efficient manner through radiant VC-based system with VC-DOAS for hot-dry and composite (ie, hot-dry with higher humidity) environment conditions. However, for warm-humid environment, complete net zero is not possible, but up to 74% of net zero target can be assured with VC-based radiant and DOAS. With respect to the conventional VC-based system, the payback period assessment for the most suitable nearly/net zero building cooling system varies in the range of 5-9 years, depending on the environmental conditions.
引用
收藏
页码:3526 / 3546
页数:21
相关论文
共 37 条
[1]   Prediction of thermal buffer zone effectiveness in real-size buildings-An experimental and analytical study [J].
Alzamil, Abdulrahman ;
Hamed, Mohamed .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2019, 43 (10) :5284-5300
[2]  
[Anonymous], 2017, ENERGYPLUS 8 7 OP SO
[3]  
[Anonymous], 2011, NRELTP550046861 US D
[4]  
Chantrasrisalai C., 2003, ASHRAE T
[5]   Experimental analysis of an evaporative-vapour compression based combined air conditioning system for required comfort conditions [J].
Chauhan, Shailendra Singh ;
Rajput, S. P. S. .
APPLIED THERMAL ENGINEERING, 2017, 115 :326-336
[6]   What is a Nearly zero energy building? Overview, implementation and comparison of definitions [J].
D'Agostino, Delia ;
Mazzarella, Livio .
JOURNAL OF BUILDING ENGINEERING, 2019, 21 :200-212
[7]  
Dekay M, CLIMATIC CONTEXT INF
[8]   Hybrid storage designs for continuous operation of solar-powered LiBr-water absorption air-conditioning [J].
El-Shaarawi, M. A. I. ;
Al-Ugla, A. A. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2016, 40 (06) :791-805
[9]   Numerical comparison between energy and comfort performances of radiant heating and cooling systems versus air systems [J].
Fabrizio, Enrico ;
Corgnati, Stefano P. ;
Causone, Francesco ;
Filippi, Marco .
HVAC&R RESEARCH, 2012, 18 (04) :692-708
[10]   Analysis and performance assessment of a new multigeneration system for net-zero energy houses [J].
Hassoun, Anwar ;
Dincer, Ibrahim .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2016, 40 (01) :36-50