Integrative modelling and optimisation of a desiccant cooling system coupled with a photovoltaic thermal-solar air heater

被引:37
作者
Fan, Wenke [1 ]
Kokogiannakis, Georgios [1 ]
Ma, Zhenjun [1 ]
机构
[1] Univ Wollongong, SBRC, Wollongong, NSW, Australia
关键词
Photovoltaic thermal collector-solar air heater; Desiccant cooling system; Design optimisation; Integrated modelling of solar desiccant systems; VAPOR COMPRESSION; PERFORMANCE; DRIVEN; WHEEL;
D O I
10.1016/j.solener.2019.10.030
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
An integrated model of a desiccant cooling system with a hybrid photovoltaic thermal collector-solar air heater (PVT-SAH) was developed and coupled with a building model to enable a performance evaluation and optimisation of the system. A double pass PVT-SAH system that incorporates heat pipes was used to increase the air temperature of the PVT-SAH outlet in order to regenerate the desiccant in a desiccant wheel. The integrated model was then used to quantify the performance of the hybrid desiccant cooling system in terms of Solar Fraction (SF) and the Coefficient of Performance (COP) and its response to the various sizes of PVT-SAH systems. The model outputs showed that the selection of the PVT-SAH design parameters can be critical in improving the system's utilisation in a desiccant cooling process. For a commercial building case study in a hot and humid climate, the annual Solar Fraction and the electrical COP of the cooling system reached up to 96.6% and up to 19.8 respectively, when the design of the PVT-SAH was optimised. The optimal electrical COP was higher than those for non-optimal designs that ranged from 0.6 to 15.1. The minimum size of the PVT-SAH that is required for the hybrid desiccant cooling system to exceed a typical COP for commercial buildings (2.6-3.0) was found to be 0.35 m(2) per m(2) of the conditioned floor area.
引用
收藏
页码:929 / 947
页数:19
相关论文
共 36 条
[1]   A novel summer air conditioning system [J].
Al-Nimr, MA ;
Abu Nabah, BA ;
Naji, M .
ENERGY CONVERSION AND MANAGEMENT, 2002, 43 (14) :1911-1921
[2]  
American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE), 2013, ASHRAE Standard 90.1-2013
[3]   Co-simulation of fuzzy control in buildings and the HVAC system using BCVTB [J].
Anastasiadi, Christina ;
Dounis, Anastasios I. .
ADVANCES IN BUILDING ENERGY RESEARCH, 2018, 12 (02) :195-216
[4]   Improvements of an unconventional desiccant air conditioning system based on experimental investigations [J].
Angrisani, G. ;
Minichiello, F. ;
Sasso, M. .
ENERGY CONVERSION AND MANAGEMENT, 2016, 112 :423-434
[5]  
[Anonymous], 2010, ASHRAE Standard, no.STANDARD62.1
[6]  
ASHRAE, 2013, 552013 ASHRAE AS, P12
[7]   Experimental assessment of a solar desiccant cooling system for an institutional building in subtropical Queensland, Australia [J].
Baniyounes, Ali M. ;
Rasul, M. G. ;
Khan, M. M. K. .
ENERGY AND BUILDINGS, 2013, 62 :78-86
[8]  
Chau C., 1995, INTERACTIVE SIMULATI
[9]   A review on photovoltaic/thermal hybrid solar technology [J].
Chow, T. T. .
APPLIED ENERGY, 2010, 87 (02) :365-379
[10]   Contributions of system components and operating conditions to the performance of desiccant cooling systems [J].
Chung, Jae Dong ;
Lee, Dae-Young .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (04) :922-927