Effects of operating room layout and ventilation system on ultrafine particle transport and deposition

被引:18
作者
D'Alicandro, Andrea Carlo [1 ]
Mauro, Alessandro [1 ]
机构
[1] Univ Napoli Parthenope, Ctr Direz, Dipartimento Ingn, Isola C4, I-80143 Naples, Italy
关键词
Air quality; Computational Fluid Dynamic (CFD); Particle deposition; Particle transport; Operating rooms; Ultrafine particles; LAMINAR AIR-FLOW; SURGICAL SMOKE; TURBULENT-FLOW; EMISSION RATES; RISK-FACTORS; DISPERSION; PARTICULATE; MODELS; CONTAMINATION; QUALITY;
D O I
10.1016/j.atmosenv.2021.118901
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The main role of Heat Ventilation and Air Conditioning (HVAC) systems in Operating Rooms (ORs) is to ensure the desired thermo-hygrometric conditions and indoor air quality, minimizing the risk of air contamination. The main sources of contamination inside ORs, during surgical operations, are Colony-Forming Units (CFUs), fine particles and ultrafine particles (UFPs), which could cause surgical site infections or health issues for the medical staff. The present work aims at increasing the scientific knowledge concerning numerical modelling of the UFP transport and deposition in ORs, analysing the effectiveness of three different ventilation systems. A numerical methodology, validated in previous works, has been used to study UFP transport and deposition inside three actual ORs, two of them equipped with a Laminar AirFlow (LAF) system and one with a Turbulent Mixing Airflow (TMA) system. Both the LAF and the TMA systems effectively evacuate the UFPs, ensuring a particle deposition rate significantly lower than the evacuation rate. The installation of extraction grilles near the surgical table allows obtaining an improvement of UFP evacuation. Due to the not perfect symmetry of OR layouts and surgical wound position, a preferred way for UFP transport can be observed. The instrument table position should be chosen consequently, to reduce UFP, CFU and contaminant deposition. The UFP concentrations at surgical staff head height cannot be neglected for health-related risks.
引用
收藏
页数:15
相关论文
共 71 条
[1]   Analyzing the risk factors influencing surgical site infections: the site of environmental factors [J].
Alfonso-Sanchez, Jose L. ;
Martinez, Isabel M. ;
Martin-Moreno, Jose M. ;
Gonzalez, Ricardo S. ;
Botia, Francisco .
CANADIAN JOURNAL OF SURGERY, 2017, 60 (03) :155-161
[2]  
ASHRAE, 2013, VENT HLTH CAR FAC
[3]  
Ball K, 1996, Todays Surg Nurse, V18, P16
[4]  
Balocco C., 2015, J BIOMED SCI ENG, V8, P7389, DOI [10.4236/jbise.2015.82008, DOI 10.4236/JBISE.2015.82008]
[5]   THERMO-FLUID DYNAMICS ANALYSIS AND AIR QUALITY FOR DIFFERENT VENTILATION PATTERNS IN AN OPERATING THEATRE [J].
Balocco, Carla ;
Petrone, Giuseppe ;
Cammarata, Giuliano .
INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2015, 33 (04) :25-32
[6]  
Balocco C, 2015, INT J VENT, V13, P351
[7]   Surgical smoke and ultrafine particles [J].
Brüske-Hohlfeld I. ;
Preissler G. ;
Jauch K.-W. ;
Pitz M. ;
Nowak D. ;
Peters A. ;
Wichmann H.-E. .
Journal of Occupational Medicine and Toxicology, 3 (1)
[8]   Airborne particle emission rates and doses received in operating rooms from surgical smoke [J].
Buonanno, G. ;
Capuano, R. ;
Cortellessa, G. ;
Stabile, L. .
BUILDING AND ENVIRONMENT, 2019, 151 :168-174
[9]  
Caretto L., 1973, P 3 INT C NUM METH F, P60, DOI [10.1007/bfb0112677, 10.1007/BFb0112677, DOI 10.1007/BFB0112677]
[10]   Modeling particle distribution and deposition in indoor environments with a new drift-flux model [J].
Chen, FZ ;
Yu, SCM ;
Lai, ACK .