Numerical study on heat transfer characteristics in branch tube type ground heat exchanger

被引:23
作者
Choi, Hoon Ki [1 ]
Yoo, Geun Jong [1 ]
Pak, Jae Hun [1 ]
Lee, Chang Hee [2 ]
机构
[1] Changwon Natl Univ, Sch Mech Engn, 20 Changwondaehak Ro, Changwon Si, Gyeongsangnam D, South Korea
[2] Songwon Univ, Sch Mech & Automot Engn, 73 Songam Ro, Gwangju, South Korea
基金
新加坡国家研究基金会;
关键词
Ground heat exchanger; Primary tube; Branch tube; 3-Dimensional numerical analysis; Heat transfer rate; Pressure drop; PUMP SYSTEM; MODEL;
D O I
10.1016/j.renene.2017.08.064
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A ground heat exchanger is an essential component of ground source heat pumps, which saves cooling and heating energy effectively. In this study, a branch tube type heat exchanger is suggested for a ground heat exchanger instead of commonly using the U-tube type for increasing heat transfer efficiency. The branch tube type heat exchanger has conjugate heat transfer including convective heat transfer between the walls of primary- and branch-tubes and internally circulating fluid, and conduction in the tube walls and grout. This conjugate heat transfer phenomenon is analyzed by steady 3-D numerical analysis using the finite volume method. In the analysis, temperature distribution, rate of heat transfer and pressure drop are compared for the branch tube type ground heat exchanger with 2, 4, 6, and 8 branch tubes together with a single U-tube type ground heat exchanger. Generally, the branch tube type shows better heat transfer performance compared to the U-tube type and the higher number of branch tubes give better heat transfer performance. Also, the branch tube type yields higher pressure drop than the U-tube type for the same mass flow rate of circulating fluid in the heat exchanger. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:585 / 599
页数:15
相关论文
共 12 条
[1]  
Bennet J., 1987, Multipole Method to Compute the Conductive Heat Flows to and Between Pipes in a Composite Cylinder. Notes on Heat Transfer 3-1987
[2]  
Cvetkovski C., 2014, Modelling of Flow and Heat Transport in Vertical Loop Ground Heat Exchangers
[3]  
De Carli M, 2010, RENEW ENERG, V35, P1537, DOI [10.1016/j.renene.2009.11.034, 10.1016/j.renene2009.11.034]
[4]   Temperature distributions in boreholes of a vertical ground-coupled heat pump system [J].
Esen, Hikmet ;
Inalli, Mustafa ;
Esen, Yuksel .
RENEWABLE ENERGY, 2009, 34 (12) :2672-2679
[5]  
Fluent, 2016, ANSYS FLUENT V 17 0
[6]   Simulation of a domestic ground source heat pump system using a three-dimensional numerical borehole heat exchanger model [J].
He, Miaomiao ;
Rees, Simon ;
Shao, Li .
JOURNAL OF BUILDING PERFORMANCE SIMULATION, 2011, 4 (02) :141-155
[7]  
Hellstrom G., 1991, Ground heat storage. Thermal analysis of Duct Storage Systems
[8]  
Ingersoll R., 1948, THEORY GROUND PIPE H, P119
[9]  
Ramadan S., 2016, PARAMETRIC STUDY VER
[10]   Vertical-borehole ground-coupled heat pumps: A review of models and systems [J].
Yang, H. ;
Cui, P. ;
Fang, Z. .
APPLIED ENERGY, 2010, 87 (01) :16-27