Real-Time Monitoring of the Vacuum Degree Based on the Partial Discharge and an Insulation Supplement Design for a Distribution Class Vacuum Interrupter

被引:3
作者
Bang, Seungmin [1 ]
Lee, Hyun-Woo [1 ]
Lee, Bang-Wook [1 ]
机构
[1] Hanyang Univ, Dept Elect & Elect Engn, HVDC EPL, Ansan 15588, South Korea
基金
新加坡国家研究基金会;
关键词
distribution class; dielectric strength; FEM; high-voltage apparatus; insulation design; partial discharge; real-time monitoring; VI; vacuum degree;
D O I
10.3390/en14237891
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The internal pressure of a vacuum interrupter (VI) is increased by arc heat, ceramic cracking, gas leakage, and manufacturing defects. Accordingly, the dielectric strength of VI rapidly decreases. To improve the reliability of power transmission, efficient maintenance through the real-time monitoring of the vacuum degree is essential. However, real-time monitoring of the vacuum degree is difficult, and related research is scarce. Additionally, due to the insulation problems of this technology, there are few commercially available products. Therefore, this paper proposes a method for real-time monitoring of the vacuum degree and an insulation supplement design for a distribution class VI. First, dielectric experiments were conducted to identify the section in which the dielectric strength of the VI rapidly decreased according to the vacuum degree. Second, for real-time monitoring of the VI, several factors were proposed through the partial discharge in the VI, while the capacitance characteristics of the VI were calculated to improve the signal of the internal partial discharge. Finally, to supplement the dielectric problems of the solid insulation high voltage apparatus that occur when real-time monitoring technology is applied, the insulation supplement design was performed through the finite element method (FEM).
引用
收藏
页数:18
相关论文
共 21 条
  • [1] The Electric Discharge Detection Method in the Low Vacuum Region of Vacuum Interrupter
    Abe, Junichi
    Tanabe, Tomoko
    Yano, Tomotaka
    Yoshida, Satoru
    Inoue, Naoaki
    [J]. ELECTRONICS AND COMMUNICATIONS IN JAPAN, 2017, 100 (01) : 59 - 66
  • [2] Consideration of the Insulation Design Method on a ±200 kV Converter Valve Unit in an HVDC Converter Hall
    Bang, Seungmin
    Kim, Ho-Seung
    Koo, Jae-Hong
    Lee, Bang-Wook
    [J]. ENERGIES, 2021, 14 (08)
  • [3] Duan XY, 2017, 2017 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT-SWITCHING TECHNOLOGY (ICEPE-ST), P880, DOI 10.1109/ICEPE-ST.2017.8188970
  • [4] Guzhov S., 2019, P 2018 REN EN POW SY, P1
  • [5] Harrouz A., 2020, 2020 9th International Conference on Renewable Energy Research and Application (ICRERA), P283, DOI 10.1109/ICRERA49962.2020.9242904
  • [6] Study on the Dielectric Characteristics of Gaseous, Liquid, and Solid Insulation Materials for a High Voltage Superconducting Apparatus
    Hong, Jonggi
    Heo, Jeong Il
    Nam, Seokho
    Kang, Hyoungku
    [J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2013, 23 (03)
  • [7] Determination of gas pressure in vacuum interrupter based on partial discharge
    Kamarol, Mohamad
    Ohtsuka, Shinya
    Hikita, Masayuki
    Saitou, Hitoshi
    Sakaki, Masayuki
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2007, 14 (03) : 593 - 599
  • [8] Lamnadi M, 2016, INT RENEW SUST ENERG, P381, DOI 10.1109/IRSEC.2016.7984079
  • [9] Mei YX, 2015, TENCON IEEE REGION
  • [10] Estimation method of degraded vacuum in vacuum interrupter based on partial discharge measurement
    Nakano, Yusuke
    Kozako, Masahiro
    Hikita, Masayuki
    Tanaka, Tsuyoshi
    Kobayashi, Masato
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (05) : 1520 - 1526