Facade flame height ejected from opening of a compartment under the coupling effect of side walls and ambient wind

被引:21
作者
Fang, Xiang [1 ]
Ren, Fei [1 ]
Zhang, Xiaolei [1 ]
Sun, Xiepeng [1 ]
Yang, Yong [1 ]
Hu, Longhua [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
Compartment fire; Facade flame; Side wall; Ambient wind; HEAT FLUXES; FIRE; CONSTRAINT; TEMPERATURE; ENTRAINMENT; BEHAVIORS;
D O I
10.1016/j.firesaf.2020.102966
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents an experimental investigation and analysis on the flame height ejected from an opening of fire compartment over the facade under the coupling effect of two side walls and ambient wind normal to the facade. Experiments were carried out in a reduced-scale model consisting of a cubic fire compartment with an opening, a facade wall and two side walls. Side walls were axi-symmetrically placed at the two sides of opening along the facade, while the opening and the facade were set normal to ambient wind generated by a wind tunnel. Facade flame heights were measured for various heat release rates, side wall distances and ambient wind speeds. Results showed that facade flame height increased as side wall distance decreased, meanwhile decreased as wind speed increased. Theoretical analysis was performed to interpret the behavior based on the air entrainment of ejected flame under their coupling effect. A global non-dimensional factor K as a function of side wall distance, ambient wind speed, the two characteristic length scales of opening as well as the dimensionless excess heat release rate was proposed to predict the facade flame height of various conditions. The experimental results were shown to be well represented.
引用
收藏
页数:9
相关论文
共 21 条
[1]  
[Anonymous], 2006, THESIS
[2]   Wind effects on smoke motion and temperature of ventilation-control led fire in a two-vent compartment [J].
Chen, Haixiang ;
Liu, Naian ;
Chow, Wanki .
BUILDING AND ENVIRONMENT, 2009, 44 (12) :2521-2526
[3]  
Coutin M., 2000, P 6 INT S FIR SAF SC, V6, P729, DOI [10.3801/IAFSS.FSS.6-729, DOI 10.3801/IAFSS.FSS.6-729]
[4]  
Fang X., 2019, P 9 INT SEM FIR EXPL, P672
[5]   Modeling thermal behaviors of window flame ejected from a fire compartment [J].
Himoto, Keisuke ;
Tsuchihashi, Tsuneto ;
Tanaka, Yoshiaki ;
Tanaka, Takeyoshi .
FIRE SAFETY JOURNAL, 2009, 44 (02) :230-240
[6]   A global non-dimensional factor characterizing side wall constraint effect on facade flame entrainment and flame height from opening of compartment fires [J].
Hu, L. H. ;
Lu, K. H. ;
Tang, F. ;
Delichatsios, M. ;
He, L. H. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 75 :122-129
[7]   Global behaviors of enclosure fire and facade flame heights in normal and reduced atmospheric pressures at two altitudes [J].
Hu, L. H. ;
Tang, F. ;
Delichatsios, M. A. ;
Wang, Q. ;
Lu, K. H. ;
Zhang, X. C. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 56 (1-2) :119-126
[8]   Facade flame height ejected from an opening of fire compartment under external wind [J].
Hu, Longhua ;
Hu, Kaizhi ;
Ren, Fei ;
Sun, Xiepeng .
FIRE SAFETY JOURNAL, 2017, 92 :151-158
[9]   A review of physics and correlations of pool fire behaviour in wind and future challenges [J].
Hu, Longhua .
FIRE SAFETY JOURNAL, 2017, 91 :41-55
[10]   An experimental study on temperature evolution inside compartment with fire growth and flame ejection through an opening under external wind [J].
Hu, Longhua ;
Ren, Fei ;
Hu, Kaizhi ;
Tang, Fei ;
Lu, Kaihua .
PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2017, 36 (02) :2955-2962