Optimization of dead tank gas circuit breaker design based on quantification of hot gas flow and dielectric properties

被引:15
作者
Uchii, T [1 ]
Nakamoto, T
Nishiwaki, S
Toyoda, A
Boggs, SA
机构
[1] TM T&D Corp, Kawasaki, Kanagawa 2100862, Japan
[2] Univ Connecticut, Elect Insulat Res Ctr, Dept Elect Engn, Storrs, CT 06269 USA
[3] Univ Connecticut, Elect Insulat Res Ctr, Dept Phys, Storrs, CT 06269 USA
[4] Univ Toronto, Dept Elect & Comp Engn, Toronto, ON, Canada
关键词
circuit breaker; dead tank breaker; gas circuit breaker; gas-insulated substation;
D O I
10.1109/TPWRD.2003.820217
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes the technologies for developing a compact and highly reliable dead-tank gas circuit breaker (GCB) on the basis of extensive data on the behavior of hot gas flow and the mechanisms of ground fault under highly inhomogeneous thermal conditions. When predicting the dielectric capability of a GCB during a large current interruption, the temperature and gas density distributions caused by the hot gas must be taken into account in addition to the electrical field imposed across the gas. Hot gas behavior was investigated quantitatively and qualitatively, to provide a basis for determining optimum exhaust tube dimensions which minimize overall circuit breaker dimensions while avoiding ground faults.
引用
收藏
页码:181 / 185
页数:5
相关论文
共 8 条
[1]   The influence of the presence of tungsten of SF6 arc plasmas [J].
Chervy, B .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1996, 29 (08) :2156-2161
[2]   Calculation of the uniform breakdown field strength of SF6 gas [J].
Cliteur, GJ ;
Hayashi, Y ;
Haginomori, E ;
Suzuki, K .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1998, 5 (06) :843-849
[3]   COMPOSITION AND TRANSPORT PROPERTIES OF SE6 AND THEIR USE IN A SIMPLIFIED ENTHALPY FLOW ARC MODEL [J].
FROST, LS ;
LIEBERMA.RW .
PROCEEDINGS OF THE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS, 1971, 59 (04) :474-&
[4]   On the hot gas exhaustion in the exhaust chamber of a gas circuit breaker after short-circuit current interruption [J].
Hayashi, Y ;
Suzuki, K ;
Haginomori, E ;
Toda, H ;
Ikeda, H .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1997, 30 (22) :3123-3130
[5]   BREAKDOWN EXPERIMENTS IN DILUTED SF6 AT ELEVATED-TEMPERATURES [J].
ROTHHARDT, L ;
MASTOVSKY, J ;
BLAHA, J .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1985, 18 (10) :L155-L157
[6]  
SAKUTA T, 1992, 10TH INT C GAS DISCH, V1, P110
[7]   Effects of hot SF6 on post-arc circuit breaker design [J].
Uchii, T ;
Nishiwaki, S ;
Boggs, S .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :124-130
[8]  
Uchii T., 2001, P IEEE POW ENG SOC W