Estimation of Time Difference Between Partial Discharge UHF Signals Using Differential Energy Method

被引:0
作者
Zhu, Ming-Xiao [1 ]
Xue, Jian-Yi [1 ]
Zhang, Jia-Ning [1 ]
Deng, Jun-Bo [1 ]
Mu, Hai-Bao [1 ]
Zhang, Guan-Jun [1 ]
Guo, An-Xiang [2 ]
Liu, Xiao-Wei [2 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian, Peoples R China
[2] State Grid Shaanxi Elect Power Co, Res Inst, Xian, Peoples R China
来源
2015 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC) | 2015年
关键词
Partial discharge; UHF method; location; time difference; differential energy; INSULATED SUBSTATIONS; LOCALIZATION; DIAGNOSTICS; LOCATION; GIS; PD;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Partial discharge (PD) site in high voltage power equipment can be located by solving the time difference equations. Estimating the time difference between PD signals with high accuracy is of great importance for accurate locating. This paper presents a time difference determining algorithm using cumulative energy function and differential energy method. The differential energy characterize the increase of cumulative energy, and the first significant peak of the differential energy is recognized as the arrival time. After that, a Monte Carlo statistics procedure is adopted to analyze the influence of noise level on the accuracy of time difference. The proposed estimation algorithm is examined with UHF signals acquired from four antennas in laboratory. The results indicate that the algorithm is effective to determine the time difference between UHF signals.
引用
收藏
页数:5
相关论文
共 14 条
[1]  
[Anonymous], 2013, IEEE T DIELECTR ELEC, V20, P2165
[2]   Determination of a Failure Probability Prognosis based on PD - Diagnostics in GIS [J].
Dreisbusch, K. ;
Kranz, H. -G. ;
Schnettler, A. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (06) :1707-1714
[3]   DIAGNOSTIC MEASUREMENTS AT UHF IN GAS INSULATED SUBSTATIONS [J].
HAMPTON, BF ;
MEATS, RJ .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1988, 135 (02) :137-144
[4]   Robust Time Delay Estimation Method for Locating UHF Signals of Partial Discharge in Substation [J].
Hou, Huijuan ;
Sheng, Gehao ;
Jiang, Xiuchen .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (03) :1960-1968
[5]   Partial discharge monitoring for power transformers using UHF sensors - part 2: Field experience [J].
Judd, MD ;
Yang, L ;
Hunter, IBB .
IEEE ELECTRICAL INSULATION MAGAZINE, 2005, 21 (03) :5-13
[6]  
Kakeeto P., 2008, 2008 INT C COND MON, P1070
[7]   Strategies for reliable automatic onset time picking of acoustic emissions and of ultrasound signals in concrete [J].
Kurz, JH ;
Grosse, CU ;
Reinhardt, HW .
ULTRASONICS, 2005, 43 (07) :538-546
[8]   A Novel Method for Ultra-High-Frequency Partial Discharge Localization in Power Transformers Using the Particle Swarm Optimization Algorithm [J].
Mirzaei, Hasan Reza ;
Akbari, Asghar ;
Gockenbach, Ernst ;
Zanjani, Mojtaba ;
Miralikhani, Karim .
IEEE ELECTRICAL INSULATION MAGAZINE, 2013, 29 (02) :26-39
[9]   Radiometric location of partial discharge sources on energized high-voltage plant [J].
Moore, PJ ;
Portugues, IE ;
Glover, IA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) :2264-2272
[10]   RF-Based Partial Discharge Early Warning System for Air-Insulated Substations [J].
Portugues, Iliana E. ;
Moore, Philip J. ;
Glover, Ian A. ;
Johnstone, Carl ;
McKosky, Ralph H. ;
Goff, Mark B. ;
van der Zel, Luke .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) :20-29