A Refined Frequency Scan Approach to Sub-Synchronous Control Interaction (SSCI) Study of Wind Farms

被引:104
|
作者
Ren, Wei [1 ]
Larsen, Einar [1 ]
机构
[1] Gen Elect, Schenectady, NY 12345 USA
关键词
Power system stability; SSCI; sub-synchronous control interaction; wind farms;
D O I
10.1109/TPWRS.2015.2501543
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Frequency-scan approaches for conducting Sub-Synchronous Control Interaction (SSCI) studies of wind farms is becoming a normal practice in the industry. Modern power electronics control used in many wind generators has a characteristic that couples two frequency components, similar to saliency effects of conventional generators. As a consequence, treating both wind farm and grid as single-dimension impedances could generate an inaccurate result. This paper describes a two-dimension transfer function approach that can be practically applied to ensure accuracy when evaluating SSCI aspects of power-electronic equipment such as renewable generation.
引用
收藏
页码:3904 / 3912
页数:9
相关论文
共 50 条
  • [1] Advanced Screening Techniques for Sub-Synchronous Interaction in Wind Farms
    Sahni, M.
    Muthumuni, D.
    Badrzadeh, B.
    Gole, A.
    Kulkarni, A.
    2012 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2012,
  • [2] Study of Sub-Synchronous Control Interaction due to the Interconnection of Wind Farms to a Series Compensated Transmission System
    Nath, Ram
    Grande-Moran, Carlos
    2012 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2012,
  • [3] Studies of sub-synchronous control interaction in wind turbine generators
    Gao, Benfeng
    Liu, Jin
    Li, Ren
    Zhao, Shuqiang
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 (16): : 154 - 161
  • [4] Sub-Synchronous Interaction Damping Control for DFIG Wind Turbines
    Leon, Andres E.
    Solsona, Jorge A.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (01) : 419 - 428
  • [5] Susceptibility of Wind Turbines to Sub-synchronous Control and Torsional Interaction
    Badrzadeh, Babak
    Saylors, Steve
    2012 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2012,
  • [6] Detection of Sub-Synchronous Control Interaction (SSCI) Using Modal Identification Analysis and FFT
    Salehi, Farshid
    Matsuo, Igor Brandao Machado
    Lee, Wei-Jen
    2018 NORTH AMERICAN POWER SYMPOSIUM (NAPS), 2018,
  • [7] REVIEW ON SUB-SYNCHRONOUS OSCILLATIONS IN WIND FARMS: ANALYSIS METHOD, STUDY SYSTEM, AND DAMPING CONTROL
    Ma, Junjie
    Liu, Fang
    Wu, Min
    Jiang, Lin
    INTERNATIONAL JOURNAL OF ROBOTICS & AUTOMATION, 2019, 34 (06): : 688 - 694
  • [8] Robust Nonlinear Controller Design for Damping of Sub-Synchronous Control Interaction in DFIG-Based Wind Farms
    Li, Penghan
    Wang, Jie
    Xiong, Linyun
    Ma, Meiling
    IEEE ACCESS, 2019, 7 : 16626 - 16637
  • [9] Sub-synchronous oscillations in wind farms - an overview study of mechanisms and damping methods
    Shi, Tong
    Nayanasiri, Dulika
    Li, Yunwei
    IET RENEWABLE POWER GENERATION, 2020, 14 (19) : 3974 - 3988
  • [10] Frequency drift of sub-synchronous oscillations caused by the DFIG wind farms when the wind speed varies
    Du, Wenjuan
    Wang, Yang
    Wang, H. F.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 103 : 317 - 325