Design of Phase Identification System to Support Three-Phase Loading Balance of Distribution Feeders

被引:29
作者
Chen, Chao-Shun [1 ,2 ]
Ku, Te-Tien [2 ]
Lin, Chia-Hung [3 ]
机构
[1] I Shou Univ, Dept Elect Engn, Kaohsiung 84008, Taiwan
[2] Natl Sun Yat Sen Univ, Dept Elect Engn, Kaohsiung 80424, Taiwan
[3] Natl Kaohsiung Univ Appl Sci, Dept Elect Engn, Kaohsiung 80778, Taiwan
关键词
Automated mapping faulty management system; global positioning system (GPS); phase identification system (PIS); POWER-FLOW;
D O I
10.1109/TIA.2011.2175352
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this paper, a phase identification system (PIS) is designed to incorporate a fuzzy microprocessor-based controller for phase measurement of underground transformers. The proposed fuzzy calibration algorithm used in the controller aims to solve the offset and gain of frequency deviation of the real-time clock, which was generated by a voltage-controlled crystal oscillator (VCXO) to maintain the timing lock with respect to the 1 pulse per second signal of the global positioning system before phase measurement is executed. According to the field test of the PIS design, the phase deviation of the real-time clock with embedded VCXO can be improved from 46.27. to 0.98. by applying the fuzzy calibration algorithm. The PIS has been applied for field measurement of underground distribution transformers to identify their phases and correct the corresponding attributes of the automated mapping faulty management (AM/FM) system in Taipower. By retrieving the information of the line segments and transformers from the AM/FM, the network modeling of distribution feeders is derived to analyze the three-phase unbalance. The rephasing strategy of laterals and distribution transformers has been derived and executed by Taipower engineers. By comparing the phase currents and neutral current of a test feeder before and after rephasing, the three-phase balance of the distribution system can be significantly enhanced with the PIS to identify the phasing of distribution transformers for deriving the rephasing strategy of the distribution feeders.
引用
收藏
页码:191 / 198
页数:8
相关论文
共 9 条
  • [1] POWER-SYSTEM APPLICATIONS FOR PHASOR MEASUREMENT UNITS
    BURNETT, RO
    BUTTS, MM
    STERLINA, PS
    [J]. IEEE COMPUTER APPLICATIONS IN POWER, 1994, 7 (01): : 8 - 13
  • [2] Three-phase power-flow by direct ZBR method for unbalanced radial distribution systems
    Chen, T. -H.
    Yang, N. -C.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2009, 3 (10) : 903 - 910
  • [3] DISTRIBUTION-SYSTEM POWER FLOW-ANALYSIS - A RIGID APPROACH
    CHEN, TH
    CHEN, MS
    HWANG, KJ
    KOTAS, P
    CHEBLI, EA
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (03) : 1146 - 1152
  • [4] Liao Ching-Jung, 1997, Monthly Journal of Taipower's Engineering, V592, P9
  • [5] An expert system for three-phase balancing of distribution feeders
    Lin, Chia-Hung
    Chen, Chao-Shun
    Chuang, Hui-Jen
    Huang, Ming-Yang
    Huang, Chia-Wen
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (03) : 1488 - 1496
  • [6] APPLICATION OF SYNCHRONIZED PHASOR MEASUREMENTS TO REAL-TIME TRANSIENT STABILITY PREDICTION
    LIU, CW
    THORP, J
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1995, 142 (04) : 355 - 360
  • [7] Milosevic B.D., 2002, IEEE Power Engineering Review, V22, P57, DOI DOI 10.1109/MPER.2002.4312578
  • [8] Synchronized phasor measurements in power systems
    Phadke, A.G.
    [J]. IEEE Computer Applications in Power, 1993, 6 (02): : 10 - 15
  • [9] STATE ESTIMATION WITH PHASOR MEASUREMENTS
    PHADKE, AG
    THORP, JS
    KARIMI, KJ
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1986, 1 (01) : 233 - 241