Utilizing data center waste heat in district heating Impacts on energy efficiency and prospects for low-temperature district heating networks

被引:167
作者
Wahlroos, Mikko [1 ]
Parssinen, Matti [2 ]
Manner, Jukka [2 ]
Syri, Sanna [1 ]
机构
[1] Aalto Univ, Sch Engn, Dept Mech Engn, POB 14100, FIN-00076 Aalto, Finland
[2] Aalto Univ, Sch Elect Engn, Dept Commun & Networking, POB 13000, FIN-00076 Aalto, Finland
关键词
District heating; Data center; Energy efficiency; Waste heat utilization; Load profile; RENEWABLE ENERGY; PERFORMANCE; RECOVERY;
D O I
10.1016/j.energy.2017.08.078
中图分类号
O414.1 [热力学];
学科分类号
摘要
Data centers seek solutions to increase energy efficiency and lower costs by novel methods. Waste heat utilization is considered to be one of the major trends in the near future, especially in the Nordic countries, where heat demand is high. In this paper, waste heat utilization was analyzed from the perspectives of both the data center and district heating network operators. Timing of the data center waste heat production was considered based on an existing data center load profile. For the district heating network operator, the system level effects of increased waste heat utilization were quantified by simulating district heating production in the city of Espoo, Finland, with actual plant and heat demand data for 2013 and 2015. Results showed that with high shares of waste heat in the district heating system, i.e. 20-60 MW, the system level operational cost savings were 0.6-7.3% in the case study. Utilizing waste heat decreased utilization hours of both combined heat and power plants and heat-only boilers. The analysis showed that pricing of the procured waste heat affects the utilization level of waste heat, but operational hours of waste heat utilization were over 95% in all scenarios. (C) 2017 The Authors Published by Elsevier Ltd.
引用
收藏
页码:1228 / 1238
页数:11
相关论文
共 39 条
[1]  
[Anonymous], EN PRIC
[2]  
[Anonymous], FINN MET I OP DAT
[3]  
[Anonymous], 2015, PRIC AND TAX
[4]  
Bash Cullen., 2007, 2007 USENIX Annual Technical Conference on Proceedings of the USENIX Annual Technical Conference, P1
[5]   Servers and data centers energy performance metrics [J].
Beitelmal, A. H. ;
Fabris, D. .
ENERGY AND BUILDINGS, 2014, 80 :562-569
[6]  
Bertoldi P., 2014, 2014 ACEEE SUMM STUD
[7]   Heat Roadmap Europe: Combining district heating with heat savings to decarbonise the EU energy system [J].
Connolly, D. ;
Lund, H. ;
Mathiesen, B. V. ;
Werner, S. ;
Moller, B. ;
Persson, U. ;
Boermans, T. ;
Trier, D. ;
Ostergaard, P. A. ;
Nielsen, S. .
ENERGY POLICY, 2014, 65 :475-489
[8]  
Customs Finland, 2015, CUST FINL EXC TAX CU
[9]   Using data centres for combined heating and cooling: An investigation for London [J].
Davies, G. F. ;
Maidment, G. G. ;
Tozer, R. M. .
APPLIED THERMAL ENGINEERING, 2016, 94 :296-304
[10]   Harnessing Renewable Energy in Cloud Datacenters: Opportunities and Challenges [J].
Deng, Wei ;
Liu, Fangming ;
Jin, Hai ;
Li, Bo ;
Li, Dan .
IEEE NETWORK, 2014, 28 (01) :48-55