Characteristics of a gas-liquid separator with a partial condenser in the absorption refrigeration cycle for automotive air conditioning

被引:0
|
作者
Suzuki, Haruka [1 ]
Sato, Yui [1 ]
Tsujimori, Atsushi [2 ]
机构
[1] Kanto Gakuin Univ, Dept Mech Engn, 1-50-1 Mutsuurahigashi, Yokohama, Kanagawa 2368501, Japan
[2] Kanto Gakuin Univ, Grad Sch, 1-50-1 Mutsuurahigashi, Yokohama, Kanagawa 2368501, Japan
来源
MECHANICAL ENGINEERING JOURNAL | 2022年 / 9卷 / 04期
关键词
Refrigeration cycle; Absorption; Partial condenser; Heat-driven; Waste heat; HEAT;
D O I
10.1299/mej.22-00001
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Experimental absorption refrigeration equipment with a generator driven by waste heat was manufactured and tested, with 2,2,2-trifluoroethane/1-methylpyrrolidine as the working fluid pair. A plate generator was used to reduce the heat transfer distance and to decrease the start-up time. However, the flow paths of the plate generator were not large enough to separate the refrigerant vapor from the two-phase flow. Therefore, a gas-liquid separator was introduced, and a cooling coil was embedded as a partial condenser in the separator to cool the refrigerant vapor and to condense the absorbent contained within it, thus increasing the concentration of the refrigerant vapor. The separator successfully separated the refrigerant from the solution in all tested conditions. The cooling rate of the partial condenser was varied from 143 to 222 W by changing the flow rate of cooling water. Then, a calculation model for the partial condenser was constructed to analyze its characteristics. In the calculation model, the helical coil partial condenser was modeled by being divided into 10 horizontal columns. It was assumed that only the solution phase had the concentration distribution from the bulk flow to the liquidvapor interface. We show that a heat and mass transfer area of 0.04 m(2) is needed to achieve an outlet vapor concentration of 0.95.
引用
收藏
页数:11
相关论文
共 7 条
  • [1] Thermodynamic analysis of a compression-absorption refrigeration air-conditioning system coupled with liquid desiccant dehumidification
    Su, Wei
    Zhang, Xiaosong
    APPLIED THERMAL ENGINEERING, 2017, 115 : 575 - 585
  • [2] Mass transfer characteristics of gas-liquid absorption during Taylor flow in mini/microchannel reactors
    Ganapathy, Harish
    Al-Hajri, Ebrahim
    Ohadi, Michael
    CHEMICAL ENGINEERING SCIENCE, 2013, 101 : 69 - 80
  • [3] A novel process for oxygen absorption from air using hollow fiber gas-liquid membrane contactor
    Banazadeh, H.
    Mousavi, S. M.
    SEPARATION AND PURIFICATION TECHNOLOGY, 2018, 193 : 283 - 288
  • [4] Numerical simulation on gas-liquid flow, heat, and mass transfer characteristics in a dual-contact-flow absorption tower
    Zhang, Yafei
    Li, Na
    Kong, Dejuan
    Zhou, Qulan
    Luo, Rui
    Xu, Tongmo
    ASIA-PACIFIC JOURNAL OF CHEMICAL ENGINEERING, 2013, 8 (06) : 849 - 861
  • [5] Experimental investigation on gas-liquid flow, heat and mass transfer characteristics in a dual-contact-flow absorption tower
    Kong, Dejuan
    Zhang, Yafei
    Li, Na
    Zhou, Qulan
    Luo, Rui
    Xu, Tongmo
    CHEMICAL ENGINEERING RESEARCH & DESIGN, 2014, 92 (01): : 13 - 24
  • [6] Energy, exergy, economic, and environment evaluations of a novel circulating liquid air energy storage system integrated with organic Rankine cycle and absorption refrigeration
    Chen, Yongan
    Zhai, Rongrong
    Li, Jingwei
    Liu, Siyuan
    Liu, Mengliang
    Xu, Yu
    Sun, Chongbao
    PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2025, 195
  • [7] Gas-liquid absorption in industrial cross-flow membrane contactors: Experimental and numerical investigation of the influence of transmembrane pressure on partial wetting
    Fougerit, Valentin
    Pozzobon, Victor
    Pareau, Dominique
    Theoleyre, Marc-Andre
    Stambouli, Moncef
    CHEMICAL ENGINEERING SCIENCE, 2017, 170 : 561 - 573