Reliability Analysis of Differential Relay as Main Protection Transformer Using Fuzzy Logic Algorithm

被引:0
|
作者
Mulyadi, Y. [1 ]
Sucita, T. [1 ]
Sumarto [1 ]
Alpani, M. [1 ]
机构
[1] Univ Pendidikan Indonesia, Dept Elect Engn Educ, Bandung, Indonesia
关键词
D O I
10.1088/1757-899X/306/1/012133
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Electricity supply demand is increasing every year. It makes PT. PLN (Persero) is required to provide optimal customer service and satisfaction. Optimal service depends on the performance of the equipment of the power system owned, especially the transformer. Power transformer is an electrical equipment that transforms electricity from high voltage to low voltage or vice versa. However, in the electrical power system, is inseparable from interference included in the transformer. But, the disturbance can be minimized by the protection system. The main protection transformer is differential relays. Differential relays working system using Kirchoff law where inflows equal outflows. If there are excessive currents that interfere then the relays will work. But, the relay can also experience decreased performance. Therefore, this final project aims to analyze the reliability of the differential relay on the transformer in three different substations. Referring to the standard applied by the transmission line protection officer, the differential relay shall have slope characteristics of 30% in the first slope and 80% in the second slope when using two slopes and 80% when using one slope with an instant time and the corresponding ratio. So, the results obtained on the Siemens differential release have a reliable slope characteristic with a value of 30 on the fuzzy logic system. In a while, ABB a differential relay is only 80% reliable because two experiments are not reliable. For the time, all the differential relays are instant with a value of 0.06 on the fuzzy logic system. For ratios, the differential relays ABB have a better value than others brand with a value of 151 on the fuzzy logic system.
引用
收藏
页数:14
相关论文
共 50 条
  • [31] A FIRANN as a differential relay for three phase power transformer protection
    Orille-Fernández, AL
    Ghonaim, NKI
    Valencia, JA
    IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (02) : 215 - 218
  • [32] Reliability Assessment of Distribution System Using Fuzzy Logic for Modelling of Transformer and Line Uncertainties
    Shokrollahi, Ahmad
    Sangrody, Hossein
    Motalleb, Mahdi
    Rezaeiahari, Mandana
    Foruzan, Elham
    Hassanzadeh, Fattah
    2017 NORTH AMERICAN POWER SYMPOSIUM (NAPS), 2017,
  • [33] Development of Algorithm for the Protection Coordination Operation of Ratio Difference Relay for Transformer Protection
    Park Y.-K.
    Eo I.-S.
    Transactions of the Korean Institute of Electrical Engineers, 2022, 71 (08): : 1182 - 1192
  • [34] Improving Differential Relay Performance during Cross-Country Fault Using a Fuzzy Logic-based Control Algorithm
    Abasi, Mahyar
    Farsani, Ahmad Torabi
    Rohani, Arash
    Shiran, Mohsen Aghazadeh
    2019 IEEE 5TH CONFERENCE ON KNOWLEDGE BASED ENGINEERING AND INNOVATION (KBEI 2019), 2019, : 193 - 199
  • [35] Adaptive fuzzy based method differential transformer protection
    2000, Amirkabir Univ Technol, Tehran, Iran (11):
  • [36] Development of Restraint Algorithm for Improvement of Reliability of Transformer Differential Protection During External Short Circuits
    Etingov, Dmitry A.
    Fedosov, Denis S.
    2019 INTERNATIONAL URAL CONFERENCE ON ELECTRICAL POWER ENGINEERING (URALCON), 2019, : 388 - 393
  • [37] Fault Diagnosis and Reliability Analysis Using Fuzzy Logic Method
    缪志农
    徐扬
    赵相瑜
    Journal of Southwest Jiaotong University, 2006, (01) : 97 - 103
  • [38] Population size adaptation for Differential Evolution algorithm using fuzzy logic
    Liu, JH
    Lampinen, J
    INTELLIGENT SYSTEMS DESIGN AND APPLICATIONS, 2003, : 425 - 436
  • [39] Incorrect Operation Accident's Analysis in Overvoltage and Differential Protection of Main Transformer Clearance
    Wang, Wei
    Han, Yu
    Yu, Hua
    Zhang, Na
    Yan, Lin
    2017 6TH DATA DRIVEN CONTROL AND LEARNING SYSTEMS (DDCLS), 2017, : 584 - 586
  • [40] Transformer Differential Protection Using Geometrical Structure Analysis of Waveforms
    Fani, B.
    Golshan, M. E. Hamedani
    Saghaian-Nejad, M.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2011, 39 (03) : 204 - 224