Reliability Analysis of Differential Relay as Main Protection Transformer Using Fuzzy Logic Algorithm

被引:0
|
作者
Mulyadi, Y. [1 ]
Sucita, T. [1 ]
Sumarto [1 ]
Alpani, M. [1 ]
机构
[1] Univ Pendidikan Indonesia, Dept Elect Engn Educ, Bandung, Indonesia
关键词
D O I
10.1088/1757-899X/306/1/012133
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Electricity supply demand is increasing every year. It makes PT. PLN (Persero) is required to provide optimal customer service and satisfaction. Optimal service depends on the performance of the equipment of the power system owned, especially the transformer. Power transformer is an electrical equipment that transforms electricity from high voltage to low voltage or vice versa. However, in the electrical power system, is inseparable from interference included in the transformer. But, the disturbance can be minimized by the protection system. The main protection transformer is differential relays. Differential relays working system using Kirchoff law where inflows equal outflows. If there are excessive currents that interfere then the relays will work. But, the relay can also experience decreased performance. Therefore, this final project aims to analyze the reliability of the differential relay on the transformer in three different substations. Referring to the standard applied by the transmission line protection officer, the differential relay shall have slope characteristics of 30% in the first slope and 80% in the second slope when using two slopes and 80% when using one slope with an instant time and the corresponding ratio. So, the results obtained on the Siemens differential release have a reliable slope characteristic with a value of 30 on the fuzzy logic system. In a while, ABB a differential relay is only 80% reliable because two experiments are not reliable. For the time, all the differential relays are instant with a value of 0.06 on the fuzzy logic system. For ratios, the differential relays ABB have a better value than others brand with a value of 151 on the fuzzy logic system.
引用
收藏
页数:14
相关论文
共 50 条
  • [21] Cause Analysis of Digital substation main transformer differential protection Misaction
    Min, Wang Tian
    Bo, Gao
    INDUSTRIAL INSTRUMENTATION AND CONTROL SYSTEMS, PTS 1-4, 2013, 241-244 : 389 - 395
  • [22] 3-PHASE DIFFERENTIAL RELAY FOR TRANSFORMER PROTECTION
    EINVALL, CH
    LINDERS, JR
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, 94 (06): : 1971 - 1980
  • [23] Fuzzy logic transformer design algorithm (FLTDA)
    Mudholkar, R.R.
    Sawant, S.R.
    Tengshe, G.G.
    Bagwan, A.B.
    Radioactive Waste Management and Environmental Restoration, 1999, 22 (01): : 17 - 29
  • [24] Analysis of successive trips of transformer differential relay and bus differential relay
    Ye, Yuanbo
    Chen, Shi
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2010, 30 (11): : 146 - 148
  • [25] Transformer differential protection using principal component analysis
    Vazquez, E.
    Mijares, I. I.
    Chacon, O. L.
    Conde, A.
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 3161 - +
  • [26] Transformer differential protection using principal component analysis
    Vazquez, Ernesto
    Mijares, Ivan
    Chacon, Oscar L.
    Conde, Arturo
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) : 67 - 72
  • [27] Misoperation of high impedance differential protection for main transformer
    Yuan, Cheng
    Tai, Nengling
    Dianli Zidonghua Shebei / Electric Power Automation Equipment, 2008, 28 (08): : 121 - 123
  • [28] A Laboratory Emulation of a Percentage Differential Protection Relay for a Single Phase Transformer using PLC
    Ismail, Shatha Y.
    Hussain, Zozan Saadallah
    Thabet, Hassaan Th H.
    Thabit, Thabit H.
    INTERNATIONAL CONFERENCE ON ELECTRICAL, COMPUTER AND ENERGY TECHNOLOGIES (ICECET 2021), 2021, : 309 - 314
  • [29] Modeling and implementing of a proposed electronic differential relay for transformer protection
    Ashour, HA
    ICEEC'04: 2004 INTERNATIONAL CONFERENCE ON ELECTRICAL, ELECTRONIC AND COMPUTER ENGINEERING, PROCEEDINGS, 2004, : 795 - 799
  • [30] Adaptive digital differential relay of parabolic characteristic for transformer protection
    Maheshwari, RP
    Verma, HK
    ELECTRIC MACHINES AND POWER SYSTEMS, 1997, 25 (05): : 459 - 473