Wavelet-based extreme learning machine for distribution grid fault location

被引:67
作者
Shafiullah, Md [1 ]
Abido, Mohammad A. [1 ]
Al-Hamouz, Zakariya [1 ]
机构
[1] King Fahd Univ Petr & Minerals, Dept Elect Engn, Dhahran 31261, Saudi Arabia
关键词
power distribution faults; power grids; learning (artificial intelligence); wavelet transforms; regression analysis; support vector machines; neural nets; fault location; distribution grid fault location; wavelet-based extreme learning machine; signal processing; machine learning tools; three-phase currents measurement; wavelet transform; statistical performance; support vector regression; SVR; artificial neural network; ANN; fault resistance; inception angle; measurement noise; thermal expansion; thermal contraction; distribution line; pre-fault loading condition; TRANSMISSION-LINE PROTECTION; POWER DISTRIBUTION-SYSTEMS; SUPPORT VECTOR MACHINE; DISTRIBUTION NETWORKS; DISTRIBUTION FEEDERS; VOLTAGE SAGS; CLASSIFICATION; REGRESSION; APPROXIMATION;
D O I
10.1049/iet-gtd.2017.0656
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Precise knowledge of faults is very exigent to reduce the outage duration as most of the customer minute losses in distribution grids occur due to longer period of interruptions caused by faults. This study proposes a fault location technique combining advanced signal processing and machine learning tools for distribution grids. The proposed technique decomposes three-phase currents measured from sending end employing wavelet transform (WT) and collects useful features to fetch them as inputs of extreme learning machine (ELM). Satisfactory values of the selected statistical performance measures validate the efficacy of proposed fault location technique. Besides, the efficacy of support vector regression (SVR) and artificial neural network (ANN) are also tested employing the WT extracted features. The presented results show the superiority of ELM-WT technique over SVR-WT and ANN-WT techniques in terms of the selected performance measures and training times. Additionally, the proposed technique is independent of fault resistance, inception angle, the presence of measurement noise, thermal expansion/contraction of the distribution line and pre-fault loading condition. Furthermore, the hybrid method detects and classifies different types of faults before locating them with different machine learning tools.
引用
收藏
页码:4256 / 4263
页数:8
相关论文
共 55 条
[1]  
[Anonymous], 2015, P 18 INT C INTELLIGE
[2]  
[Anonymous], 2019, IEEE T POWER DELIVER, DOI DOI 10.1109/TPWRD.2019.2891538
[3]  
[Anonymous], 2014 11 IEEE IAS INT
[4]  
[Anonymous], 2012, IEEE PES C EXPOSITIO
[5]  
Arvind Pratul, 2012, 2012 IEEE Symposium on Computers & Informatics, P113, DOI 10.1109/ISCI.2012.6222677
[6]  
Awalin LJ, 2012, PRZ ELEKTROTECHNICZN, V88, P206
[7]   Transmission line conductor temperature impact on state estimation accuracy [J].
Bockarjova, Marija ;
Andersson, Goeran .
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, :701-706
[8]   On the use of continuous-wavelet transform for fault location in distribution power systems [J].
Borghetti, A. ;
Corsi, S. ;
Nucci, C. A. ;
Paolone, M. ;
Peretto, L. ;
Tinarelli, R. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2006, 28 (09) :608-617
[9]  
Boser B. E., 1992, Proceedings of the Fifth Annual ACM Workshop on Computational Learning Theory, P144, DOI 10.1145/130385.130401
[10]   Statistical Approaches to Concept-Level Sentiment Analysis Introduction [J].
Cambria, Erik ;
Schuller, Bjoern ;
Liu, Bing ;
Wang, Haixun ;
Havasi, Catherine .
IEEE INTELLIGENT SYSTEMS, 2013, 28 (03) :6-9