Proposed methodology for online frequency response analysis based on magnetic coupling to detect winding deformations in transformers

被引:19
|
作者
Cheng, Yangchun [1 ]
Bi, Jiangang [2 ]
Chang, Wenzhi [2 ]
Xu, Yuan [2 ]
Pan, Xiaohua [3 ]
Ma, Xianwei [4 ]
Chang, Shuai [5 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] China Elect Power Res Inst, Inst High Voltage Technol, Beijing 100192, Peoples R China
[3] Linyi Power Supply Co, State Grid Shandong Elect Power Co, Linyi 276000, Shandong, Peoples R China
[4] State Grid Beijing Elect Power Co, Cable Branch, Beijing 100020, Peoples R China
[5] State Grid Jiangsu Elect Power Co, Changzhou Power Supply Co, Changzhou 213000, Peoples R China
关键词
bushings; frequency response; transformer windings; power transformers; coils; sensors; mechanical variables measurement; deformation; excitation signal; response signal; magnetic field coupling; frequency sweep signal; Rogowski coil sensor; high-voltage bushing; power station; strong electromagnetic power frequency noise; magnetic coupling; winding deformation detection; online frequency response curve online analysis; response current signal measurement; voltage; 72; 5; kV; 35; 0; 110; 10; FRA; VOLTAGE;
D O I
10.1049/hve.2019.0134
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Frequency response analysis is widely used as a method for the offline diagnosis of winding deformations in power transformers. To apply it to a working transformer, people need to determine how to inject the excitation signal and measure the response signal for windings that bear a rated voltage and current. In this study, a method to obtain the frequency response curve online is proposed. It uses the principle of magnetic field coupling to inject a frequency sweep signal into the windings through a Rogowski coil. Another Rogowski coil sensor placed at the root of a high-voltage bushing is used to measure the response current signal. Experiments on a 72.5 kV bushing show that metal accessories of the bushing have no influence on the injection or the measurement. The feasibility of this method was verified by experiments on charged 110/35/10 kV transformers at a factory and a working 35 kV transformer in a power station. The results show that it is safe to install the Rogowski coil at the root of the high-voltage bushing. The excitation signal can be injected into live windings and the response signal is measurable. Strong electromagnetic power frequency noise can be reduced and the frequency response curve can be measured online.
引用
收藏
页码:343 / 349
页数:7
相关论文
共 50 条
  • [1] Sweep frequency response analysis method as a diagnostic tool to detect windings deformations in power transformers
    Ludwikowski, Karol
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (10): : 47 - 49
  • [2] Survey of Frequency Response Analysis on Winding Deformation of Transformers
    Li, Zhenhua
    Zhang, Yangpo
    Zhu, Binxin
    Luo, Yufei
    Zhang, Tao
    Zhang, Zhi
    2019 4TH INTERNATIONAL CONFERENCE ON INTELLIGENT GREEN BUILDING AND SMART GRID (IGBSG 2019), 2019, : 567 - 571
  • [3] Power frequency magnetic field interference suppression method for online frequency response analysis of power transformers
    Cheng, Yangchun
    Liu, Xiangdong
    Sha, Yufei
    Chang, Wenzhi
    Bi, Jiangang
    JOURNAL OF ENGINEERING-JOE, 2024, 2024 (07):
  • [4] Evaluation of Statistical Interpretation Methods for Frequency Response Analysis based Winding Fault Detection of Transformers
    Wesley, Neoh-Khoo
    Bhandari, Saurabh
    Subramaniam, Aravinth
    Bagheri, Mehdi
    Panda, S. K.
    2016 IEEE INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY TECHNOLOGIES (ICSET), 2016, : 36 - 41
  • [5] A frequency-response-based characterisation methodology for piezoelectric transformers
    Horsley, E. L.
    Foster, M. P.
    Stone, D. A.
    ESTC 2008: 2ND ELECTRONICS SYSTEM-INTEGRATION TECHNOLOGY CONFERENCE, VOLS 1 AND 2, PROCEEDINGS, 2008, : 959 - 962
  • [6] Platform for studying online frequency response analysis of power transformers
    Rampersad, Ravi
    Singh, Arvind
    Bahadoorsingh, Sanjay
    Sharma, Chandrabhan
    2015 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2015, : 57 - 60
  • [7] A Hybrid Winding Model of Disc-Type Power Transformers for Frequency Response Analysis
    Shintemirov, A.
    Tang, W. H.
    Wu, Q. H.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) : 730 - 739
  • [8] Sweep frequency response analysis (SFRA) for the assessment of winding displacements and deformation in power transformers
    Secue, J. R.
    Mombello, E.
    ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (06) : 1119 - 1128
  • [9] Electromagnetic transients modelling of split-winding traction transformers for frequency response analysis
    Sobouti, Mohammad Amin
    Azizian, Davood
    Bigdeli, Mehdi
    Gharehpetian, Gevork B.
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2019, 13 (09) : 1362 - 1371
  • [10] The Application of Sweep Frequency Response Analysis for the Online Monitoring of Power Transformers
    Rahimpour, Hossein
    Mitchell, Steve
    Tusek, Joe
    PROCEEDINGS OF THE 2016 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2016,