Investigation on Frequency Response Analysis Measurement Method for Power Transformer Impedance

被引:0
|
作者
Ishizaka, Kohei [1 ]
Koshizuka, Tadashi [1 ]
Ikeda, Hisatoshi [2 ]
Taniguchi, Yasuhiko [2 ]
Haginomori, Eiichi [2 ]
机构
[1] Tokyo Denki Univ, Fac Engn, Dept Elect & Elect Engn, Tokyo, Japan
[2] Univ Tokyo, APET, Tokyo, Japan
来源
2016 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D) | 2016年
关键词
transformer; frequency response; impedance; condition diagnosis;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The frequency response analysis of transformer has been expected to be a good method for diagnosing the transformer condition. As the transformer impedance is affected by the configuration, the change of the impedance will be a good indicator for the change of the transformer configuration. The method which has been recognized cannot achieve the measurement of current flowing through the stray capacitance to the earth. The measured impedance was not correct at the high frequency range where an influence of the capacitance becomes large. In this paper, the new method was proposed in which the resistor for the current measurement is connected to the terminal of the power application and its value is adjusted. It is shown that the correct measurement can be achieved by the proposed one document.
引用
收藏
页数:5
相关论文
共 50 条
  • [1] Frequency Response Measurement of a Power Transformer
    Ariastina, W. G.
    Kumara, I. N. S.
    Partha, C. G. Indra
    Arjana, I. G. Dyana
    2015 INTERNATIONAL CONFERENCE QUALITY IN RESEARCH (QIR), 2015, : 102 - 105
  • [2] Optical Frequency-Response Analysis for Power Transformer
    Ma, Guoming
    Liu, Yunpeng
    Li, Yabo
    Fan, Xiaozhouce
    Xu, Ce
    Qin, Weiqi
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (03) : 1562 - 1570
  • [3] Understanding Power Transformer Frequency Response Analysis Signatures
    Abu-Siada, A.
    Hashemnia, N.
    Islam, S.
    Masoum, Mohammad A. S.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2013, 29 (03) : 48 - 56
  • [4] Diagnosis Method of Power Transformer Winding Position Deviation based on Frequency Response Analysis
    Song, Xi
    Zhang, Hehui
    Li, Wenhui
    Liu, Jixiang
    Song, Renping
    Wang, Bo
    Yin, Qiang
    Journal of Network Intelligence, 2022, 7 (01): : 243 - 259
  • [5] Using the Vibration Frequency Response Analysis Method to Detect the Winding Deformation of Power Transformer
    Wang, F. H.
    Jin, Z. J.
    2011 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING, 2011,
  • [6] High Frequency Power Transformer Modelling for Frequency Response Analysis Studies
    Aljohani, O.
    Abu-Siada, A.
    Lie, Shengtao
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 291 - 294
  • [7] A Contribution to the Frequency Analysis and Transient Response of Power Transformer Windings
    Saied, Mohamed Mostafa
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2014, 42 (11) : 1143 - 1151
  • [8] A Review of Frequency Response Analysis Methods for Power Transformer Diagnostics
    Alsuhaibani, Saleh
    Khan, Yasin
    Beroual, Abderrahmane
    Malik, Nazar Hussain
    ENERGIES, 2016, 9 (11)
  • [9] An Experimental Study of the Sweep Frequency Impedance Method on the Winding Deformation of an Onsite Power Transformer
    Wang, Song
    Wang, Shuang
    Cui, Ying
    Long, Jie
    Ren, Fuqiang
    Ji, Shengchang
    Wang, Shuhong
    ENERGIES, 2020, 13 (14)
  • [10] Windings of a Power Transformer, Its Frequency Response and FEM Analysis
    Pradhan, Sihabrata
    Nayak, Sisir Kumar
    2020 3RD INTERNATIONAL CONFERENCE ON ENERGY, POWER AND ENVIRONMENT: TOWARDS CLEAN ENERGY TECHNOLOGIES (ICEPE 2020), 2021,