Arc flash calculations in systems protected by low-voltage circuit breakers

被引:4
|
作者
Gregory, GD [1 ]
Lyttle, I
Wellman, CM
机构
[1] Square D Co, Cedar Rapids, IA 52404 USA
[2] DuPont Co Inc, Wilmington, DE 19880 USA
关键词
arc flash; circuit breaker (CB); flash protection boundary; incident energy;
D O I
10.1109/TIA.2003.813721
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
A series of previous papers has provided information regarding the are flash hazard and methods of calculating its potential impact on persons working on or near the equipment. This paper extends that base of information by focusing on the arcing current level and duration in low-voltage circuits protected by circuit breakers (CBs). It describes a method of calculating incident energy and the flash protection boundary due to arcing occurrences in equipment protected by CBs. This method provides convenient procedures for determining these values for generic situations in which some details of the CB are not known. Further, it provided a process for determining these values in typical feeder and branch circuit applications involving common transformers and cable sizes and lengths. The values are needed to determine safe work practices and appropriate Personal Protective Equipment to comply with NFPA 70E, Standard for Electrical Safety Requirements for Employee Workplaces.
引用
收藏
页码:1193 / 1199
页数:7
相关论文
共 50 条
  • [31] Low-Voltage Power Circuit Breakers and Molded Case Circuit Breakers - a comparison of test requirements
    Kimblin, Clive W.
    Long, R.William
    Conference Record of Industrial and Commercial Power Systems Technical Conference, 1999,
  • [32] Improvements of protective characteristics of automatic low-voltage circuit breakers
    Rainin V.E.
    Kobozev A.S.
    Russian Electrical Engineering, 2009, 80 (02) : 102 - 108
  • [33] Testing Low-Voltage Circuit Breakers for Ultimate Breaking Capacity
    Vasiliev S.A.
    Egorov E.G.
    Egorov G.E.
    Kadyshev E.N.
    Kulagina A.G.
    Luiya N.Y.
    Nikiforov I.K.
    Russian Electrical Engineering, 2021, 92 (08) : 412 - 416
  • [34] NEW INTERNATIONAL STANDARD FOR LOW-VOLTAGE CIRCUIT-BREAKERS
    ROBBINS, JA
    ELECTRICAL REVIEW, 1973, 193 (17): : 569 - 570
  • [35] A new optical technique for investigations of low-voltage circuit breakers
    Hong, D
    Sandolache, G
    Bauchire, JM
    Gentils, F
    Fleurier, C
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2005, 33 (02) : 976 - 981
  • [36] Differences in low-voltage fused and unfused power circuit breakers
    Hinton, ST
    2005 IEEE Industrial and Commercial Power Systems Technical Conference, Conference Record, 2005, : 77 - 80
  • [37] Complex criteria of operation of automatic low-voltage circuit breakers
    V. E. Rainin
    A. S. Kobozev
    Russian Electrical Engineering, 2012, 83 (5) : 237 - 242
  • [38] TRANSIENT RECOVERY VOLTAGE IN SHORT-CIRCUIT TESTS ON LOW-VOLTAGE CIRCUIT-BREAKERS
    BOTTAUSCIO, O
    CROTTI, G
    FARINA, G
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER ENGINEERING, 1991, 1 (05): : 267 - 270
  • [39] Design of a sense circuit for low-voltage flash memories
    Tanzawa, T
    Takano, Y
    Taura, T
    Atsumi, S
    IEEE JOURNAL OF SOLID-STATE CIRCUITS, 2000, 35 (10) : 1415 - 1421
  • [40] Service-life evaluations of low-voltage power circuit breakers and molded-case circuit breakers
    Sprague, MJ