An analysis of operating parameters in the cooling tower-based thermally activated building system

被引:6
作者
Samuel, D. G. Leo [1 ]
Nagendra, S. M. Shiva [2 ]
Maiya, M. P. [1 ]
机构
[1] Indian Inst Technol Madras, Dept Mech Engn, Madras, Tamil Nadu, India
[2] Indian Inst Technol Madras, Dept Civil Engn, Madras, Tamil Nadu, India
关键词
Passive cooling; Thermally activated building system; Cooling tower; Parametric analysis; Operative temperature; Thermal comfort; LOW-ENERGY OFFICE; AIR; COMFORT; TEMPERATURE; PERFORMANCE; SIMULATION; HEAT; TABS;
D O I
10.1177/1420326X17704276
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Thermally activated building system is not only energy efficient but also provides better thermal comfort compared to the conventional cooling systems. In this paper, COMSOL Multiphysics, a computational fluid dynamics tool, is used to simulate the performance of a cooling tower coupled with thermally activated building system for the hot and dry summer climatic conditions of New Delhi. The effects of three operating parameters, namely, temperature and inlet velocity of water and the number of cooling surfaces (area), on the performance of the system have been investigated. The results indicate that increasing the water inlet temperature from wet bulb temperature (WBT) to WBT + 6celcius would increase the operative temperature of the indoor space, a thermal comfort index, by 2celcius. The increase in water inlet velocity from 0.2 to 1 m/s would decrease the diurnal average of operative temperature by 1.4celcius. If only the roof was cooled, the diurnal average of operative temperature was 36.7celcius. The diurnal average of operative temperature was reduced by 5.7celcius if all the building fabrics were cooled. In this case, with pipes connected in series from the floor first to walls and then to roof resulted in 2.9celcius lower operative temperature compared to that in the reverse sequence. Hence, the sequence in which the fabrics are cooled would have an appreciable influence on the performance of thermally activated building system.
引用
收藏
页码:1175 / 1186
页数:12
相关论文
共 30 条
  • [1] Barnard CL, 1996, BIOPHYS J, V6, P717, DOI DOI 10.1016/S0006-3495(66)86690-0
  • [2] Deneen MA, 2010, BUS EC, V45, P126
  • [3] Fanger P.O., 1982, Thermal comfort
  • [4] Fanger PO, 1970, THERMAL COMFORT
  • [5] Helsen L, 2016, WOODHEAD PUBL SER EN, P423, DOI 10.1016/B978-0-08-100311-4.00015-7
  • [6] Incropera F.P., 2010, FUNDAMENTAL HEAT MAS
  • [7] Numerical simulation of radiant floor cooling system: The effects of thermal resistance of pipe and water velocity on the performance
    Jin, Xing
    Zhang, Xiaosong
    Luo, Yajun
    Cao, Rongquan
    [J]. BUILDING AND ENVIRONMENT, 2010, 45 (11) : 2545 - 2552
  • [8] Lurie M.V, 2008, Modeling of Oil Product and Gas Pipeline Transportation, DOI DOI 10.4310/CDM.2008.V2008.N1.A3
  • [9] MEIERHANS RA, 1993, ASHRAE TRAN, V99, P511
  • [10] Meierhans RA, 1996, ASHRAE TRAN, V102, P693