A novel Single-phase-to-ground fault identification and isolation strategy in wind farm collector line

被引:23
作者
Jin, Neng [1 ]
Xing, Jiawei [1 ]
Liu, Yao [1 ]
Li, Zhengtian [1 ]
Lin, Xiangning [1 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Elect Engn & Technol, Wuhan 430074, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
Single-phase-to-ground fault; Wind farm collector system; D-S evidence theory; Overvoltage; Fault isolation; ALGORITHM; SELECTION; NETWORK;
D O I
10.1016/j.ijepes.2017.06.031
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The collector system of wind farm is a non-effectively grounding (small current grounding) system, where the single-phase-to-ground fault can easily develop into a three-phase fault, and without timely identification and isolation, it may cause incalculable hazard to wind farms. In fact, the present fault identification methods based on single fault characteristic quantity or majority voting rule all have certain limitations when dealing with some certain faults theoretically. Furthermore, the wind turbine could be possibly exposed to overvoltage several times of the rated voltage after the fault isolation by direct switching off the grid-side breaker in collector line. To solve these problems, this paper first analyzes the mechanism of overvoltage by constructing the resonance model of wind farm with distributed parameter. A novel single-phase-to-ground fault identification method based on D-S evidence theory is proposed. Then two flexible fault isolation methods are further proposed. Simulation results verify the validity and superiority of the proposed strategy. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:15 / 26
页数:12
相关论文
共 29 条
[1]   Control design and dynamic performance analysis of a wind turbine-induction generator unit [J].
Abdin, ES ;
Xu, W .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2000, 15 (01) :91-96
[2]  
[Anonymous], 2005, WIND POWER POWER SYS
[3]  
[Anonymous], IEEE T APPL SUPERCON
[4]   Power quality and stability improvement of a wind farm using STATCOM supported with hybrid battery energy storage [J].
Arulampalam, A. ;
Barnes, M. ;
Jenkins, N. ;
Ekanayake, J. B. .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2006, 153 (06) :701-710
[5]  
Atabakhsh M, 2014, INT J INNOV TECHNOL, V4, P10
[6]  
Bouaguel W, 2013, 2013 INTERNATIONAL CONFERENCE ON COMPUTER APPLICATIONS TECHNOLOGY (ICCAT)
[7]  
Guan J.W., 1991, EVIDENCE THEORY ITS
[8]   Feature selection for content-based image retrieval [J].
Guldogan, Esin ;
Gabbouj, Moncef .
SIGNAL IMAGE AND VIDEO PROCESSING, 2008, 2 (03) :241-250
[9]   STATCOM impact study on the integration of a large wind farm into a weak loop power system [J].
Han, Chong ;
Huang, Alex Q. ;
Baran, Mesut E. ;
Bhattacharya, Subliashish ;
Litzenberger, Wayne ;
Anderson, Loren ;
Johnson, Anders L. ;
Edris, Abdel-Aty .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2008, 23 (01) :226-233
[10]   Wide-Area Backup Protection Algorithm Based on Fault Component Voltage Distribution [J].
He, Zhiqin ;
Zhang, Zhe ;
Chen, Wei ;
Malik, Om P. ;
Yin, Xianggen .