Computation of transient overvoltages in low-voltage installations during direct strikes to different lightning protection systems

被引:25
|
作者
Metwally, Ibrahim A. [1 ]
Heidler, Fridolin H.
机构
[1] Sultan Qaboos Univ, Coll Engn, Dept Elect & Comp Engn, Muscat 123, Oman
[2] Univ Fed Armed Forces, Fac Elect Engn, D-85577 Munich, Germany
关键词
direct strike; lightning-induced voltage; lightning protection system (LPS); loop termination; negative subsequent current; transient analysis;
D O I
10.1109/TEMC.2007.902192
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a numerical electromagnetic analysis of loop-termination voltages inside an outer lightning protection system (LPS) resulting from direct lightning strikes. The method of moments is combined with the transmission line model, and employed to model the whole structure in three dimensions and the lightning channel, respectively. Three distinct standard LPS classes and a nonstandard LPS are modeled, namely, LPS1, LPS2, and LPS4, and LPS0, respectively. All cases are simulated using the negative subsequent stroke current at lightning protection level 11 according to IEC 62305-1. Three distinct current waveforms are selected in order to simulate the variety of different current rises. Three single-phase parallel vertical loops are simulated inside the struck LPS. The results reveal that reducing the LPS mesh width improves its shielding performance, where this may be a basic method to damp the lightning-induced voltages with little dependency on the strike location, and without any appreciable effect of the LPS material. The variation of the lightning-current front shows that the loop-termination voltages are altered within a factor of about 2. Existence and interconnection of extra protective earthing, e.g., via information technology cables, and the value and type of the loop-termination impedance also have significant influence on such voltages.
引用
收藏
页码:602 / 613
页数:12
相关论文
共 50 条
  • [21] Low-voltage electrical and lightning protection installation in facilities accredited
    Jezercic, I. Aurer
    KEMIJA U INDUSTRIJI-JOURNAL OF CHEMISTS AND CHEMICAL ENGINEERS, 2018, 67 (5-6): : 286 - 288
  • [22] Modeling and protection of photovoltaic systems during lightning strikes: A review
    Hetita, Ibrahim
    Zalhaf, Amr S.
    Mansour, Diaa-Eldin A.
    Han, Yang
    Yang, Ping
    Wang, Congling
    RENEWABLE ENERGY, 2022, 184 : 134 - 148
  • [23] Overvoltages in cable systems of large building during direct lightning stroke
    Markowska, Renata
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (03): : 143 - 145
  • [24] Analysis of the protection of low voltage installations against induced lightning over voltages
    Daguillon, O
    Zeddam, A
    Rochereau, H
    Michaud, J
    ELECTROMAGNETIC COMPATIBILITY 1996 - THIRTEENTH INTERNATIONAL WROCLAW SYMPOSIUM, 1996, : 527 - 531
  • [25] LIGHTNING INDUCED VOLTAGES ON LOW-VOLTAGE LINES WITH DIFFERENT CONFIGURATIONS
    Piantini, A.
    Janiszewski, J. M.
    2010 30TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2010,
  • [26] Effective Protection Distances of Low-Voltage SPD With Different Voltage Protection Levels
    He, Jinliang
    Yuan, Zhiyong
    Wang, Shunchao
    Hu, Jun
    Chen, Shuiming
    Zeng, Rong
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) : 187 - 195
  • [27] Risk estimation of low-voltage power system and equipments during direct lightning strike to structure
    Sowa, Andrzej
    Kuczynski, Tomasz
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (03): : 104 - 105
  • [28] Application of RCD and AFDD in low-voltage electrical installations for protection against fire
    Czapp, Stanislaw
    PRZEGLAD ELEKTROTECHNICZNY, 2019, 95 (11): : 12 - 16
  • [29] Protection of low-voltage auxiliary electrical installations of power plants from faults
    Bespalov A.V.
    Borisova E.S.
    Gusev O.Yu.
    Gusev Yu.P.
    Starshinov V.A.
    Power Technology and Engineering, 2005, 39 (3) : 179 - 186
  • [30] Lightning protection design for low voltage distribution systems
    Asakawa, Akira