Research on the Lightning Intruding Overvoltage and Protection Measures of 500 kV AC Fault Current Limiter

被引:5
|
作者
Chen, Changfu [1 ]
Han, Yongxia [1 ]
Liu, Junxiang [2 ]
Mo, Wenxiong [2 ]
Yuan, Zhao [3 ]
Huang, Jianning [1 ]
Su, Haibo [2 ]
Zhang, Xiancong [2 ]
Wu, Kaijian [3 ]
机构
[1] South China Univ Technol, Sch Elect Power, Guangzhou 510641, Guangdong, Peoples R China
[2] Guangzhou Power Supply Co Ltd, Test & Res Inst, Guangzhou 514010, Guangdong, Peoples R China
[3] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, Wuhan 430074, Hubei, Peoples R China
基金
国家重点研发计划;
关键词
fault current limiter; overvoltage; high coupled split reactor; shunt capacitor; lightning impulse withstand voltage; TOWER;
D O I
10.3390/en12203845
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
As one of the key technologies to solve the problem of high short-circuit current, the fault current limiter (FCL) has become a research hotspot in China and abroad. The overvoltage and protection measures of the FCL are the key technologies for its application. Therefore, this paper studies the lightning intruding overvoltage and protection measures for a 500 kV FCL based on a high coupled split reactor (HCSR). Firstly, according to the main topology of the system and the 500 kV HCSR-FCL structure, the lightning intruding overvoltage simulation model of the 500 kV station, including the nearby transmission lines, is established on the PSCAD (Power Systems Computer Aided Design) program. Secondly, the lightning overvoltage of the equipment in the station and the components of the HCSR-FCL are simulated and analyzed when the transmission lines nearby are subjected to lightning shielding failure and back flashover. Meanwhile, the influence of the HCSR-FCL on the lightning overvoltage of the equipment in the station are compared and analyzed before and after the HCSR-FCL is installed. The simulation results show that the overvoltage of the equipment in the station and the components of the HCSR-FCL is more serious when the shielding failure occurs in the transmission lines nearby. The HCSR-FCL can reduce the lightning overvoltage of the equipment in the station, but the maximum inter-terminal and inter-arm lightning overvoltage of the HCSR can reach 1064 kV and 790 kV, respectively, under the current limiting state and the current sharing state. Finally, methods of increasing the arresters on the transmission lines side of the HCSR-FCL and shunt capacitor between each module of the HCSR-FCL are proposed to reduce the lightning overvoltage. The lightning impulse withstand voltage of each component of the HCSR is also proposed: The inter-terminal lightning impulse withstand voltage of HCSR is 170 kV. The inter-arm lightning impulse withstand voltage of HCSR is 200 kV. The terminal-to-ground lightning impulse withstand voltage of the HCSR-FCL is 1550 kV.
引用
收藏
页数:17
相关论文
共 50 条
  • [41] Parameter Design of Fault Current Limiter for High Voltage AC System Considering Transient Component of Short Circuit Current
    Liu, Jiawei
    Yuan, Jiaxin
    Zhou, Hang
    Li, Xüzhe
    Mo, Zuoquan
    Gaodianya Jishu/High Voltage Engineering, 2024, 50 (08): : 3769 - 3782
  • [42] Modeling and Test Validation of a 15kV 24MVA Superconducting Fault Current Limiter
    Moriconi, Franco
    Koshnick, Nick
    De la Rosa, Francisco
    Singh, Amandeep
    2010 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION: SMART SOLUTIONS FOR A CHANGING WORLD, 2010,
  • [43] Design and test results of 66 kV high-Tc superconducting fault current limiter magnet
    Yazawa, T.
    Ootani, Y.
    Sakai, M.
    Otsuki, M.
    Kuriyarna, T.
    Urata, M.
    Tokunaga, Y.
    Inoue, K.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2006, 16 (02) : 683 - 686
  • [44] Electrical insulation design of 13.2 kV/630 a bifilar winding type HTS fault current limiter
    Seok, Bok-Yeol
    Kang, Hyoungku
    Lee, Chanjoo
    Nam, Kwanwoo
    Kim, Yong-Han
    Ko, Tae Kuk
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2007, 17 (02) : 1505 - 1508
  • [45] Thyristor-Controlled AC Reactor Based Fault Current Limiter for Distribution Network Stability Enhancement
    Radmanesh, Hamid
    Fathi, S. H.
    Gharehpetian, G. B.
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2016, 11 (05) : 1070 - 1076
  • [46] Method to secure the performance of the differential protection in presence of fault current limiter applied into the neutral line
    Sahebi, Ali
    Samet, Haidar
    Ghanbari, Teymoor
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2016, 10 (08) : 880 - 888
  • [47] Three phase inductive HTS fault current limiter for the protection of a 12 kVA synchronous generator
    Vajda, I
    Semperger, S
    Porjesz, T
    Szalay, A
    Meerovich, V
    Sokolovsky, V
    Gawalek, W
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2001, 11 (01) : 2515 - 2518
  • [48] Research on Relieving Voltage Sag of Sensitive Load Node Based on Fault Current Limiter
    Ma, Li
    Zhou, Qian
    2016 INTERNATIONAL SYMPOSIUM ON COMPUTER, CONSUMER AND CONTROL (IS3C), 2016, : 858 - 861
  • [49] Research on a New Type of Fault Current Limiter Based on High Coupled Split Reactor
    Mo, Wenxiong
    Liu, Junxiang
    Wang, Yong
    Gan, Lin
    Su, Haibo
    Zhu, Lu
    Qiao, Shengya
    Wu, Kaijian
    Yuan, Zhao
    PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1, 2020, 598 : 1513 - 1522
  • [50] Research on optimal configuration of fault current limiter based on reliability in large power network
    Zeng, Jianjun
    Zhang, Yonggao
    ARCHIVES OF ELECTRICAL ENGINEERING, 2020, 69 (03) : 661 - 677