Research on the Lightning Intruding Overvoltage and Protection Measures of 500 kV AC Fault Current Limiter

被引:5
|
作者
Chen, Changfu [1 ]
Han, Yongxia [1 ]
Liu, Junxiang [2 ]
Mo, Wenxiong [2 ]
Yuan, Zhao [3 ]
Huang, Jianning [1 ]
Su, Haibo [2 ]
Zhang, Xiancong [2 ]
Wu, Kaijian [3 ]
机构
[1] South China Univ Technol, Sch Elect Power, Guangzhou 510641, Guangdong, Peoples R China
[2] Guangzhou Power Supply Co Ltd, Test & Res Inst, Guangzhou 514010, Guangdong, Peoples R China
[3] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, Wuhan 430074, Hubei, Peoples R China
基金
国家重点研发计划;
关键词
fault current limiter; overvoltage; high coupled split reactor; shunt capacitor; lightning impulse withstand voltage; TOWER;
D O I
10.3390/en12203845
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
As one of the key technologies to solve the problem of high short-circuit current, the fault current limiter (FCL) has become a research hotspot in China and abroad. The overvoltage and protection measures of the FCL are the key technologies for its application. Therefore, this paper studies the lightning intruding overvoltage and protection measures for a 500 kV FCL based on a high coupled split reactor (HCSR). Firstly, according to the main topology of the system and the 500 kV HCSR-FCL structure, the lightning intruding overvoltage simulation model of the 500 kV station, including the nearby transmission lines, is established on the PSCAD (Power Systems Computer Aided Design) program. Secondly, the lightning overvoltage of the equipment in the station and the components of the HCSR-FCL are simulated and analyzed when the transmission lines nearby are subjected to lightning shielding failure and back flashover. Meanwhile, the influence of the HCSR-FCL on the lightning overvoltage of the equipment in the station are compared and analyzed before and after the HCSR-FCL is installed. The simulation results show that the overvoltage of the equipment in the station and the components of the HCSR-FCL is more serious when the shielding failure occurs in the transmission lines nearby. The HCSR-FCL can reduce the lightning overvoltage of the equipment in the station, but the maximum inter-terminal and inter-arm lightning overvoltage of the HCSR can reach 1064 kV and 790 kV, respectively, under the current limiting state and the current sharing state. Finally, methods of increasing the arresters on the transmission lines side of the HCSR-FCL and shunt capacitor between each module of the HCSR-FCL are proposed to reduce the lightning overvoltage. The lightning impulse withstand voltage of each component of the HCSR is also proposed: The inter-terminal lightning impulse withstand voltage of HCSR is 170 kV. The inter-arm lightning impulse withstand voltage of HCSR is 200 kV. The terminal-to-ground lightning impulse withstand voltage of the HCSR-FCL is 1550 kV.
引用
收藏
页数:17
相关论文
共 50 条
  • [31] Conceptual Design of a 24 kV, 1 kA Resistive Superconducting Fault Current Limiter
    Noe, Mathias
    Hobl, Achim
    Tixador, Pascal
    Martini, Luciano
    Dutoit, Bertrand
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2012, 22 (03)
  • [32] Development of 6.6 kV/600 A superconducting fault current limiter using coated conductors
    Yazawa, T.
    Koyanagi, K.
    Takahashi, M.
    Toba, K.
    Takigami, H.
    Urata, M.
    Iijima, Y.
    Saitoh, T.
    Amemiya, N.
    Shiohara, Y.
    Ito, T.
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2009, 469 (15-20): : 1740 - 1744
  • [33] A practical study of the 66-kV fault current limiter (FCL) system with rectifier
    Tokuda, Noriaki
    Matsubara, Yoshio
    Yuguchi, Kyosuke
    Ohkuma, Takesi
    Hobara, Natsuro
    Takahashi, Yoshihisa
    ELECTRICAL ENGINEERING IN JAPAN, 2007, 160 (03) : 12 - 18
  • [34] Estimation of AC transport current loss generated in Bi2223 bulk for fault current limiter
    Noda, T
    Shimizu, H
    Yokomizu, Y
    Matsumura, T
    Murayama, N
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2002, 378 : 823 - 826
  • [35] Research on a Secondary Active Limiting DC Fault Current Limiter Topology
    Chen, Hechong
    Yuan, Jiaxin
    Xu, Shunkai
    Zou, Chunhang
    Hong, Yonggui
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (12) : 14547 - 14561
  • [36] Design of 6.6 kV, 100 A saturated DC reactor type superconducting fault current limiter
    Hoshino, T
    Salim, KM
    Kawasaki, A
    Muta, I
    Nakamura, T
    Yamada, M
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) : 2012 - 2015
  • [37] 66 kV/1 kA High-Tc superconducting fault current limiter magnet
    Yazawa, T
    Ootani, Y
    Sakai, M
    Kuriyama, T
    Urata, M
    Tokunaga, Y
    Inoue, K
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2005, 15 (02) : 2059 - 2062
  • [38] Cryostat for 66 kV/750 a high-Tc superconducting fault current limiter magnet
    Ohtani, Y
    Yazawa, T
    Kurita, S
    Kuriyama, T
    Nomura, S
    Ohkuma, T
    Hobara, N
    Takahashi, Y
    Inoue, K
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2004, 14 (02) : 855 - 858
  • [39] Development of 66 kV/750 A High-Tc superconducting fault current limiter magnet
    Yazawa, T
    Ootani, Y
    Sakai, M
    Kuriyama, T
    Nomura, S
    Ohkuma, T
    Hobara, N
    Takahashi, Y
    Inoue, K
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2004, 14 (02) : 786 - 790
  • [40] Design and test results of 4.6 kV high-Tc superconducting fault current limiter
    Yazawa, T
    Yoneda, E
    Matsuzaki, J
    Shimada, M
    Kuriyama, T
    Nomura, S
    Ohkuma, T
    Sato, Y
    Takahashi, Y
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2001, 11 (01) : 2511 - 2514