Thermodynamic analysis and optimization of a CO2 based transcritical refrigeration system with an ejector

被引:0
作者
Ahammed, Md. Ezaz [1 ]
Bhattacharyya, Souvik [1 ]
Ramgopal, Maddali [1 ]
机构
[1] IIT Kharagpur, Dept Mech Engn, Kharagpur, W Bengal, India
来源
DYNAMICS OF MACHINES AND MECHANISMS, INDUSTRIAL RESEARCH | 2014年 / 592-594卷
关键词
ejector; carbon dioxide; refrigeration; specific piston displacement rate; COP; 2-PHASE EJECTOR; CYCLE; PERFORMANCE;
D O I
10.4028/www.scientific.net/AMM.592-594.1825
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
In the present paper some results obtained from the thermodynamic analysis of a CO2 based transcritical refrigeration system are presented. The system studied uses an ejector as an expansion device in place of the conventional throttle valve. Results are obtained considering constant pressure mixing process in the mixing chamber of the ejector. The compressor discharge pressure and ejector entrainment ratio are optimized for maximum COP. The required compressor displacement rate per ton of refrigeration (specific piston displacement rate, PD) is calculated at the optimum conditions. A correlation is obtained for PD in terms of the evaporator, gas cooler exit and ejector efficiencies. From the sensitivity analysis it is seen that of all the parameters, the PD is most sensitive to evaporator temperature.
引用
收藏
页码:1825 / 1831
页数:7
相关论文
共 11 条
[1]  
[Anonymous], 2003, 21CR61010030 ARTI
[2]   Experimental study on R-134a refrigeration system using a two-phase ejector as an expansion device [J].
Chaiwongsa, Praitoon ;
Wongwises, Somchai .
APPLIED THERMAL ENGINEERING, 2008, 28 (5-6) :467-477
[3]   Particular characteristics of transcritical CO2 refrigeration cycle with an ejector [J].
Deng, Jian-qiang ;
Jiang, Pei-xue ;
Lu, Tao ;
Lu, Wei .
APPLIED THERMAL ENGINEERING, 2007, 27 (2-3) :381-388
[4]   Experimental investigation on the performance of the refrigeration cycle using a two-phase ejector as an expansion device [J].
Disawas, S ;
Wongwises, S .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (06) :587-594
[5]  
Kornhauser AA., 1990, P USNC IIR PURD REFR
[6]   Transcritical CO2 refrigeration cycle with ejector-expansion device [J].
Li, DQ ;
Groll, EA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (05) :766-773
[7]   Experimental investigation on the effect of mixing length on the performance of two-phase ejector for CO2 refrigeration cycle with and without heat exchanger [J].
Nakagawa, M. ;
Marasigan, A. R. ;
Matsukawa, T. ;
Kurashina, A. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (07) :1604-1613
[8]   Performance analysis of the vapour compression cycle using ejector as an expander [J].
Nehdi, E. ;
Kairouani, L. ;
Bouzaina, M. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2007, 31 (04) :364-375
[9]   Efficiencies of transcritical CO2 cycles with and without an expansion turbine [J].
Robinson, DM ;
Groll, EA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (07) :577-589
[10]   Optimization of ejector-expansion transcritical CO2 heat pump cycle [J].
Sarkar, Jahar .
ENERGY, 2008, 33 (09) :1399-1406