Performance comparison of occupancy count estimation and prediction with common versus dedicated sensors for building model predictive control

被引:36
作者
Sangogboye, Fisayo Caleb [1 ]
Arendt, Krzysztof [1 ]
Singh, Ashok [1 ]
Veje, Christian T. [1 ]
Kjaergaard, Mikkel Baun [1 ]
Jorgensen, Bo Norregaard [1 ]
机构
[1] Univ Southern Denmark, Ctr Energy Informat, Odense, Denmark
关键词
occupancy prediction; occupancy estimation; machine learning; model predictive control; CLIMATE CONTROL; SIMULATION; METHODOLOGIES; BEHAVIOR;
D O I
10.1007/s12273-017-0397-5
中图分类号
O414.1 [热力学];
学科分类号
摘要
Model predictive control is a promising approach to optimize the operation of building systems and provide demand-response functionalities without compromising indoor comfort. The performance of model predictive control relies, among other things, on the quality of weather forecasts and building occupancy predictions. The present study compares the accuracy and computational demand of two occupancy estimation and prediction approaches suitable for building model predictive control: (1) count prediction based on indoor climate modeling and parameter estimation "using common sensors", (2) count prediction based on data from 3D stereovision camera. The performance of the two approaches was tested in two rooms of a case study building. The results show that the method with dedicated sensors outperforms common sensors. However, if a building is not equipped with dedicated sensors, the present study shows that the common sensor method can be a satisfactory alternative to be used in model predictive control.
引用
收藏
页码:829 / 843
页数:15
相关论文
共 37 条
[1]   Estimating occupancy in heterogeneous sensor environment [J].
Amayri, Manar ;
Arora, Abhay ;
Ploix, Stephane ;
Bandhyopadyay, Sanghamitra ;
Quoc-Dung Ngo ;
Badarla, Venkata Ramana .
ENERGY AND BUILDINGS, 2016, 129 :46-58
[2]  
[Anonymous], 2011, P 2011 S SIM ARCH UR
[3]  
[Anonymous], 2011, P INT MOD C
[4]  
Arendt K., 2016, P IEEE SMARTGRIDCOMM
[5]  
Arendt K, 2016, P 12 REHVA WORLD C C, V8
[6]  
Bonvini M., 2014, P 10 INT MOD C LUND, P647, DOI DOI 10.3384/ECP14096647
[7]   Recursive parameter estimation of thermostatically controlled loads via unscented Kalman filter [J].
Burger, Eric M. ;
Moura, Scott J. .
SUSTAINABLE ENERGY GRIDS & NETWORKS, 2016, 8 :12-25
[8]   Statistical analysis and modeling of occupancy patterns in open-plan offices using measured lighting-switch data [J].
Chang, Wen-Kuei ;
Hong, Tianzhen .
BUILDING SIMULATION, 2013, 6 (01) :23-32
[9]   A fusion framework for occupancy estimation in office buildings based on environmental sensor data [J].
Chen, Zhenghua ;
Masood, Mustafa K. ;
Soh, Yeng Chai .
ENERGY AND BUILDINGS, 2016, 133 :790-798
[10]   Using existing network infrastructure to estimate building occupancy and control plugged-in devices in user workspaces [J].
Christensen, Ken ;
Melfi, Ryan ;
Nordman, Bruce ;
Ben Rosenblum ;
Viera, Raul .
INTERNATIONAL JOURNAL OF COMMUNICATION NETWORKS AND DISTRIBUTED SYSTEMS, 2014, 12 (01) :4-29