Use of Rusck Formula and Multi-Nonlinear Regression to Discard Events Required to Calculate the Lightning Performance of Overhead Lines

被引:0
|
作者
Soto, Edison [1 ]
Perez, Ernesto [2 ]
del Rio, Diego [3 ]
机构
[1] Univ Ind Santander, Escuela Ingn Elect Elect & Telecomunicac, Bucaramanga 680002, Colombia
[2] Univ Nacl Colombia, Dept Energia Elect & Automat, Medellin 50037, Colombia
[3] Univ Nacl Colombia, Dept Ingn Elect Elect & Comp, Manizales 111321, Colombia
关键词
Mathematical models; Lightning; Surges; Conductivity; Computational modeling; Monte Carlo methods; Transformers; Heuristic techniques; lightning-induced voltages; flashover rate; lightning performance; overhead lines; POWER DISTRIBUTION LINES; INDUCED VOLTAGES; FLASHOVER RATES; MODEL;
D O I
10.1109/TPWRD.2021.3131542
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this work, two heuristic techniques used to reduce the number of simulations of lightning-induced voltages, which are required to assess the lightning performance of distribution lines according to the Monte Carlo methodology, are presented. The first uses the Rusck Formula to discard the events that do not cause damage to the line. The second is based on a multi-nonlinear regression of the previously simulated events. Both techniques were applied to estimate the flashover rate of straight and complex lines above flat ground with finite conductivities. As a result, between 80 % to 90 % of the total number of simulations were eliminated with a reduced error.