A new non-communication protection technique for transmission lines

被引:110
作者
Bo, ZQ [1 ]
机构
[1] Univ Bath, Sch Elect & Elect Engn, Bath BA2 7AY, Avon, England
关键词
transmission line; non-communication protection; transient based protection;
D O I
10.1109/61.714458
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a new non-communication protection technique for transmission lines. The technique relies on firstly detection of fault generated high frequency current transient signals. A specially designed multi-channel filter unit is then applied to the captured signals to extract desired bands of high frequency signals. Comparison between the spectral energies of different bands of the filter outputs determines whether a fault is internal or external to the protected zone. in addition to the saving in costs through negating the need for a communication link, the technique also retains many advantages of the 'transient based protection' technology, such as insensitivity to fault type, fault position, fault path resistance and fault inception angle. It is also not affected by CT saturation, the power frequency short-circuit level at the terminating busbar or the precise configuration of the source side networks.
引用
收藏
页码:1073 / 1078
页数:6
相关论文
共 9 条