Breakdown voltage characteristics of combined air gaps under negative lightning impulse

被引:1
作者
Wu, Shaocheng [1 ,2 ]
Wang, Linong [1 ,2 ]
Gao, Jiachen [1 ,2 ]
Xie, Cheng [1 ,2 ]
Song, Bin [1 ]
Peng, Yong [2 ]
Liu, Jianben [2 ]
Liu, Yan [2 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan 430000, Peoples R China
[2] State Key Lab Power Grid Environm Protect, Wuhan 430076, Peoples R China
关键词
Combined air gaps; Negative lightning impulse; Breakdown voltage; Breakdown timing; DISCHARGE CHARACTERISTICS;
D O I
10.1016/j.egyr.2022.08.047
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Long air gaps are the main external insulation medium of overhead transmission lines. When there are floating conductors in the air gap, the gap's configuration changes, and the combined air gaps is formed. We built an experimental platform to obtain the breakdown characteristics of a 2 m rod-plane air gap with a rod floating conductor in different positions under negative lightning impulse. The results show that as the distance between the floating conductor and the high voltage conductor changes, the breakdown voltage (BV) and timing change. Moreover, the breakdown voltage increases with the length of sub-gap 1, showing a trend of first increasing, then decreasing, and then increasing, which is different from the trend under positive lightning impulse. The reason for this phenomenon is inferred from the analysis to be related to the polarity effect. (C) 2022 Published by Elsevier Ltd.
引用
收藏
页码:1230 / 1236
页数:7
相关论文
共 22 条
[1]  
[Anonymous], 2010, HIGH VOLTAGE TEST TE
[2]   BIRD STREAMER FLASHOVERS ON FPL TRANSMISSION-LINES [J].
BURNHAM, JT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (02) :970-977
[3]   Leader channel models for long air positive electrical discharges [J].
Diaz, Oscar ;
Arevalo, Liliana ;
Cooray, Vernon .
JOURNAL OF ELECTROSTATICS, 2015, 76 :208-215
[4]   A Modified Model for Discharge Voltage of AC Transmission Line-Tower Air Gaps [J].
Fang, Yaqi ;
Wang, Linong ;
Li, Rui ;
Zhang, Qiushi ;
Gao, Jiachen ;
Song, Bin .
IEEE ACCESS, 2019, 7 :71472-71480
[5]   Effect of a floating conductor on discharge characteristics of a long air gap under switching impulse [J].
Gao, Jiachen ;
Wang, Linong ;
Wu, Shaocheng ;
Xie, Cheng ;
Tan, Qipeng ;
Ma, Guoqiang ;
Tueraili, Hayinaer ;
Song, Bin .
JOURNAL OF ELECTROSTATICS, 2021, 114
[6]   Engineering model of dielectric strength in phase-to-phase air gaps [J].
Gao, Jiachen ;
Wang, Linong ;
Lian, Zhangxiang ;
Li, Guanlin ;
Fang, Yaqi ;
Song, Bin .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (19) :4179-4185
[7]   Discharge of Air Gaps During Ground Potential Live-Line Work on Transmission Lines [J].
Gao, Jiachen ;
Wang, Linong ;
Li, Guanlin ;
Fang, Yaqi ;
Song, Bin ;
Xiao, Bin ;
Liu, Kai .
ELECTRIC POWER SYSTEMS RESEARCH, 2020, 187
[8]   Switching impulse discharge characteristics of UHV transmission line air gaps [J].
Gao, Jiachen ;
Wang, Linong ;
Zhang, Qiushi ;
Song, Bin ;
Liu, Kai ;
Xiao, Bin .
IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2019, 14 (05) :735-741
[9]   Modeling of Positive Switching Impulse Discharge of UHV Transmission Line Air Gaps [J].
Gao, Jiachen ;
Wang, Linong ;
Zhang, Qiushi ;
Song, Bin .
APPLIED SCIENCES-BASEL, 2018, 8 (12)
[10]  
Guan G., 2003, Fundamentals of High Voltage Engineering