Determination of the Ostwald coefficient of dissolved gases in transformer oil with gas chromatography

被引:0
作者
Zhao, JH
Wang, HL
Yang, P
Guan, YF [1 ]
机构
[1] Chinese Acad Sci, Dalian Inst Chem Phys, Dept Analyt Chem & Microinstrumentat, Dalian 116012, Peoples R China
[2] Jinxi Lianhua Petrochem Corp, Huludao 125001, Peoples R China
关键词
dissolved gas analysis; Ostwald coefficient; gas chromatography;
D O I
暂无
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
An apparatus is designed and evaluated for the determination of the Ostwald coefficient of gases dissolved in transformer oil. It consists of a water bath with magnetic stirring, balance flask, six-port valve and an on-line gas chromatography. The balance time and Ostwald coefficient of hydrocarbon gases including CH,, C-2 H-2, C2H4, C2H6 and C3H8 dissolved in transformer oil were determined at 20° C and 50° C, respectively. The error of repeatability of 8 measurements is less than 1. 2% ( RSD). It provides fundamental data for online measurement of dissolved gases in transformer oil by gas chromatography.
引用
收藏
页码:471 / 474
页数:4
相关论文
共 7 条
[1]  
American Society for Testing and Materials ASTM G32, 1998, ANN BOOK ASTM STAND
[2]  
ASTM, 1983, ANN BOOK ASTM STAND
[3]  
CHINESE STANDARD OFF, 2001, Patent No. 72522001
[4]  
Galand J., 1972, Revue Generale de l'Electricite, V81, P727
[5]  
*IEC, 1992, IEC PUBL, V567
[6]   Simultaneous determination of dissolved gases and moisture in mineral insulating oils by static headspace gas chromatography with helium photoionization pulsed discharge detection [J].
Jalbert, J ;
Gilbert, R ;
Tétreault, P .
ANALYTICAL CHEMISTRY, 2001, 73 (14) :3382-3391
[7]   STATIC HEADSPACE GAS-CHROMATOGRAPHIC DETERMINATION OF FAULT GASES DISSOLVED IN TRANSFORMER INSULATING OILS [J].
LEBLANC, Y ;
GILBERT, R ;
DUVAL, M ;
HUBERT, J .
JOURNAL OF CHROMATOGRAPHY, 1993, 633 (1-2) :185-193