Digital distance relaying algorithm for first-zone protection for parallel transmission lines

被引:67
作者
Liao, Y [1 ]
Elangovan, S [1 ]
机构
[1] Natl Univ Singapore, Dept Elect Engn, Singapore 119260, Singapore
关键词
distance protection; algorithm; parallel transmission lines;
D O I
10.1049/ip-gtd:19982181
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper proposes a new digital distance relaying algorithm for first-zone protection for parallel transmission lines. The new method uses data from one end of the protected parallel lines to calculate the fault distance. It is shown that the new method is independent of fault resistance, remote infeed and source impedances. Extensive simulation studies using EMTP have verified that this approach can obtain a highly accurate fault distance estimation within one cycle after fault inception and hence is very much suitable for digital distance protection for parallel lines. Applications of this method for fault location are also presented.
引用
收藏
页码:531 / 536
页数:6
相关论文
共 8 条
[1]  
Horowitz S., 1992, Power System Relaying. Research Studies Press Ltd
[2]  
LEUVEN KU, 1987, ALTERNATIVE TRANSIEN
[3]  
LEWIS WA, 1947, AIEE T, V66, P694
[4]   Unsynchronized two-terminal fault location estimation [J].
Novosel, D ;
Hart, DG ;
Udren, E ;
Garitty, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) :130-138
[5]   A NEW COMPUTER-BASED INTEGRATED DISTANCE RELAY FOR PARALLEL TRANSMISSION-LINES [J].
PHADKE, AG ;
JIHUANG, L .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (02) :445-452
[6]  
UNGRAD H, 353014 E CHES BROWN
[7]   Design implementation and performance evaluation of a new digital distance relaying algorithm [J].
Waikar, DL ;
Liew, AC ;
Elangovan, S .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (01) :448-456
[8]   INFLUENCE OF MUTUAL COUPLING BETWEEN PARALLEL CIRCUITS ON SETTING OF DISTANCE PROTECTION [J].
WHEELER, SA .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1970, 117 (02) :439-&