Real-Time Hardware-in-the-Loop Testing of IEC 61850 GOOSE-Based Logically Selective Adaptive Protection of AC Microgrid

被引:27
作者
Memon, Aushiq Ali [1 ]
Kauhaniemi, Kimmo [1 ]
机构
[1] Univ Vaasa, Sch Technol & Innovat, Vaasa 65200, Finland
关键词
Microgrids; Testing; Power system stability; Load modeling; Generators; Voltage control; Real-time systems; Adaptive protection; AC microgrid; logic selectivity; IEC; 61850; GOOSE; real-time simulation; HIL testing; converter-based DERs; battery storage; POWER-ELECTRONICS; CO-SIMULATION; SYSTEMS; COMMUNICATION; INVERTER; FRAMEWORK; DESIGN;
D O I
10.1109/ACCESS.2021.3128370
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The real-time (RT) hardware-in-the-loop (HIL) simulation-based testing is getting popular for power systems and power electronics applications. The HIL testing provides the interactive environment between the actual power system components like control and protection devices and simulated power system networks including different communication protocols. Therefore, the results of the RT simulation and HIL testing before the actual implementation in the field are generally more acceptable than offline simulations. This paper reviews the HIL testing methods and applications in the recent literature and presents a step-by-step documentation of a new HIL testing setup for a specific case study. The case study evaluates real-time implementation of previously proposed communication-dependent logically selective adaptive protection algorithm of AC microgrids using HIL testing of IEC 61850 generic object-oriented substation event (GOOSE) protocol. The RT model of AC microgrid including the converter-based distributed energy resources and battery storage along with IEC 61850 GOOSE protocol implementation is created in MATLAB/Simulink and RT-LAB software using OPAL-RT simulator platform. Local area network (LAN) at the laboratory acts as IEC 61850 station bus for exchanging GOOSE Boolean signals between the RT target and the actual digital relay. The evaluation of the round-trip delay using the RT simulation has been performed. It is found that the whole process of fault detection, isolation and adaptive setting using Ethernet communication is possible within the standard low voltage ride through curve maintaining the seamless transition to the islanded mode. The signal monitoring inside the relay is suggested to avoid false tripping of the relay.
引用
收藏
页码:154612 / 154639
页数:28
相关论文
共 106 条
[1]   IEC 61850 based substation automation system: A survey [J].
Aftab, Mohd Asim ;
Hussain, S. M. Suhail ;
Ali, Ikbal ;
Ustun, Taha Selim .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 120
[2]   Performance evaluation of IEC 61850 GOOSE-based inter-substation communication for accelerated distance protection scheme [J].
Aftab, Mohd Asim ;
Roostaee, Saeed ;
Hussain, S. M. Suhail ;
Ali, Ikbal ;
Thomas, Mini S. ;
Mehfuz, Shabana .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (18) :4089-4098
[3]   A review on real-time simulation and analysis methods of microgrids [J].
AhmadiAhangar, Roya ;
Rosin, Argo ;
Niaki, Ali Nabavi ;
Palu, Ivo ;
Korotko, Tarmo .
INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2019, 29 (11)
[4]   Communication Modeling for Differential Protection in IEC-61850-Based Substations [J].
Ali, Ikbal ;
Hussain, S. M. Suhail ;
Tak, Ashok ;
Ustun, Taha Selim .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2018, 54 (01) :135-142
[5]   IEC 61850-based adaptive protection system for the MV distribution smart grid [J].
Alvarez de Sotomayor, A. ;
Della Giustina, D. ;
Massa, G. ;
Dede, A. ;
Ramos, F. ;
Barbato, A. .
SUSTAINABLE ENERGY GRIDS & NETWORKS, 2018, 15 :26-33
[6]  
[Anonymous], 2011, OP5600 HILBOX US GUI
[7]  
[Anonymous], 2016, OPWP150620SAREVA OPA
[8]  
[Anonymous], 2014, OP5330 US GUID DIG A
[9]  
[Anonymous], 400-kW Grid-Connected PV Farm (Average Model)
[10]  
[Anonymous], 2016, VAMP 50 VAMP 52 VAMP