Evaluation of the Impact of Including the Frequency-Dependent Behavior of Grounding Systems on the Lightning Performance of Transmission Lines and on Grounding Systems Design

被引:2
|
作者
Vasconcellos, Felipe [1 ]
Alipio, Rafael [2 ]
Moreira, Fernando [3 ]
机构
[1] Univ Fed Bahia, Superintendency Environm & Infrastruct, Salvador, BA, Brazil
[2] Ctr Technol Educ Minas Gerais, Dept Elect Engn, Belo Horizonte, MG, Brazil
[3] Univ Fed Bahia, Dept Elect & Comp Engn, Salvador, BA, Brazil
关键词
Overhead lines; Lightning performance; Grounding systems; Frequency dependance; Grounding systems design; IMPULSE EFFICIENCY;
D O I
10.1007/s40313-021-00833-7
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper evaluates the impact of including the frequency-dependent behavior of grounding systems on the lightning performance of transmission lines and on their grounding systems design. The developed overvoltages through the insulator strings and the backflashover rates of a typical 138 kV transmission line are estimated, while the tower-grounding system is represented by two different models, namely: (i) a static model, consisting of a lumped resistance with value equal to the low-frequency grounding resistance, (ii) an impulse impedance model (based on the accurate HEM-Hybrid Electromagnetic Model). A method is proposed to define the length of the counterpoise wires of the transmission line as a function of the soil resistivity. The criterion used was to limit the value of the impulse impedance to 20 ohm which is similar to that adopted by Brazilian power utilities, although they usually adopt this value for the low-frequency resistance of grounding, thus disregarding its frequency-dependent characteristics. From the results obtained, it can be concluded that disregarding the frequency-dependent effect of transmission line grounding leads to errors in estimating their lightning performance. It was also found that by using a more sophisticated modeling for grounding, it would be possible to optimize the design of transmission line grounding systems, reducing the length of the counterpoise wires, therefore resulting in supply and labor gains.
引用
收藏
页码:531 / 540
页数:10
相关论文
共 50 条
  • [41] Evaluation of the Backflashover Performance of a 150 kV Overhead Transmission Line Considering Frequency- and Current-Dependent Effects of Tower Grounding Systems
    Datsios, Zacharias G.
    Stracqualursi, Erika
    Patsalis, Diamantis G.
    Araneo, Rodolfo
    Mikropoulos, Pantelis N.
    Tsovilis, Thomas E.
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2024, 60 (02) : 2611 - 2620
  • [42] The effect of wide band modeling of tower-footing grounding system on the lightning performance of transmission lines: A probabilistic evaluation
    Shariatinasab, Reza
    Gholinezhad, Jayad
    Sheshyekani, Keyhan
    Alemi, Mohamad Reza
    ELECTRIC POWER SYSTEMS RESEARCH, 2016, 141 : 1 - 10
  • [43] TRANSIENT PERFORMANCE OF SUBSTATION GROUNDING SYSTEMS SUBJECTED TO LIGHTNING AND SIMILAR SURGE CURRENTS
    XIONG, W
    DAWALIBI, FP
    IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (03) : 1412 - 1420
  • [44] Analysis of Transient Performance of Grounding System Considering Frequency-Dependent Soil Parameters and Ionization
    Moradi, Mohamad
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2020, 62 (03) : 785 - 797
  • [45] Lightning transient performance analysis of substation based on complete transmission line model of power network and grounding systems
    Zeng, R
    Kang, P
    He, JL
    Zhang, B
    Chen, SM
    Zou, J
    IEEE TRANSACTIONS ON MAGNETICS, 2006, 42 (04) : 875 - 878
  • [46] Comments on "Time-Domain Modeling of Grounding Systems' Impulse Response Incorporating Nonlinear and Frequency-Dependent Aspects"
    Mohammadpur, Sahar
    Moradi, Mohamad
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2020, 62 (01) : 296 - 297
  • [47] Analysis of Soil Resistivity and its Impact on Grounding Systems Design
    Malanda, Sindisiwe C.
    Davidson, Innocent E.
    Buraimoh, Elutunji
    Singh, Eddie
    2018 IEEE PES/IAS POWERAFRICA CONFERENCE, 2018, : 324 - 329
  • [48] The Effect of Frequency Dependence of Soil Electrical Parameters on the Lightning Performance of Typical Wind-Turbine Grounding Systems
    Alipio, Rafael
    Conceicao, Daiane
    Dias, Rosilene N.
    Visacro, Silverio
    Yamamoto, Kazuo
    2017 INTERNATIONAL SYMPOSIUM ON LIGHTNING PROTECTION (XIV SIPDA), 2017, : 353 - 358
  • [49] Frequency and transient behavior of grounding systems I - Physical and methodological aspects
    Portela, C
    IEEE 1997 INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY - SYMPOSIUM RECORD, 1997, : 379 - 384
  • [50] Frequency and transient behavior of grounding systems II - Practical application examples
    Portela, C