Evaluation of the Impact of Including the Frequency-Dependent Behavior of Grounding Systems on the Lightning Performance of Transmission Lines and on Grounding Systems Design

被引:2
|
作者
Vasconcellos, Felipe [1 ]
Alipio, Rafael [2 ]
Moreira, Fernando [3 ]
机构
[1] Univ Fed Bahia, Superintendency Environm & Infrastruct, Salvador, BA, Brazil
[2] Ctr Technol Educ Minas Gerais, Dept Elect Engn, Belo Horizonte, MG, Brazil
[3] Univ Fed Bahia, Dept Elect & Comp Engn, Salvador, BA, Brazil
关键词
Overhead lines; Lightning performance; Grounding systems; Frequency dependance; Grounding systems design; IMPULSE EFFICIENCY;
D O I
10.1007/s40313-021-00833-7
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper evaluates the impact of including the frequency-dependent behavior of grounding systems on the lightning performance of transmission lines and on their grounding systems design. The developed overvoltages through the insulator strings and the backflashover rates of a typical 138 kV transmission line are estimated, while the tower-grounding system is represented by two different models, namely: (i) a static model, consisting of a lumped resistance with value equal to the low-frequency grounding resistance, (ii) an impulse impedance model (based on the accurate HEM-Hybrid Electromagnetic Model). A method is proposed to define the length of the counterpoise wires of the transmission line as a function of the soil resistivity. The criterion used was to limit the value of the impulse impedance to 20 ohm which is similar to that adopted by Brazilian power utilities, although they usually adopt this value for the low-frequency resistance of grounding, thus disregarding its frequency-dependent characteristics. From the results obtained, it can be concluded that disregarding the frequency-dependent effect of transmission line grounding leads to errors in estimating their lightning performance. It was also found that by using a more sophisticated modeling for grounding, it would be possible to optimize the design of transmission line grounding systems, reducing the length of the counterpoise wires, therefore resulting in supply and labor gains.
引用
收藏
页码:531 / 540
页数:10
相关论文
共 50 条
  • [21] Lightning Performance of Transmission Lines: Methodology to Design Grounding Electrodes to Ensure an Expected Outage Rate
    Visacro, Silverio
    Silveira, Fernando H.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) : 237 - 245
  • [22] Analysis of the lightning impulse and low-frequency performance of wind farm grounding systems
    Alipio, Rafael
    Correia de Barros, Maria Teresa
    Schroeder, Marco Aurelio O.
    Yamamoto, Kazuo
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 180
  • [23] Evaluation of the transmission tower and frequency-dependent soil parameters influence on the grounding potential rise waveforms
    Schroeder, Marco Aurelio O.
    Moura, Rodolfo A. R.
    Assis, Fernando A.
    Paulino, Jose O. S.
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 222
  • [24] The Response of Grounding Electrodes to Lightning Currents: The Effect of Frequency-Dependent Soil Resistivity and Permittivity
    Visacro, Silverio
    Alipio, Rafael
    Murta Vale, Maria Helena
    Pereira, Clever
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2011, 53 (02) : 401 - 406
  • [25] THE RESPONSE GROUNDING ELECTRODES TO LIGHTNING CURRENTS: THE EFFECT OF FREQUENCY-DEPENDENT RESISTIVITY AND PERMITTIVITY OF SOIL
    Visacro, Silverio
    Murta Vale, M. H.
    Guimaraes N, Miguel B.
    Araujo, Roger A.
    Pinto, Wyllian L. F.
    Alipio, Rafael S.
    2010 30TH INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2010,
  • [26] The Impact of Apparent Frequency-Dependent Soil Properties on Electrical Grounding Characteristics
    Kuklin, Dmitry
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2022, 64 (06) : 2122 - 2130
  • [27] Analysis of Transmission Lines With Arrester Termination, Considering the Frequency-Dependence of Grounding Systems
    Sheshyekani, Keyhan
    Sadeghi, Seyed Hossein Hesamedin
    Moini, Rouzbeh
    Rachidi, Farhad
    Paolone, Mario
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2009, 51 (04) : 986 - 994
  • [28] Frequency dependent and transient characteristics of substation grounding systems
    Grcev, LD
    Heimbach, M
    IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) : 172 - 178
  • [29] Frequency dependent and transient characteristics of substation grounding systems
    Univ `St. Cyril and Methodius', Skopje, Mk
    IEEE Trans Power Delivery, 1 (172-178):
  • [30] Transient grounding behavior considering frequency-dependent soil parameters: field versus transmission line theories
    Schroeder, Marco A. O.
    Amaral, Amanda B.
    Moura, Rodolfo A. R.
    Barros, Maria T. C.
    Lima, Antonio C. S.
    2017 IEEE 3RD GLOBAL ELECTROMAGNETIC COMPATIBILITY CONFERENCE (GEMCCON), 2017,