Transients induced on control cables and secondary circuit of instrument transformers in a GIS during switching operations

被引:23
作者
Rao, M. Mohana [1 ]
Thomas, M. Joy
Singh, B. P.
机构
[1] Bharat Heavy Elect Ltd, Corp R&D, Hyderabad 500093, Andhra Pradesh, India
[2] Indian Inst Sci, Dept High Voltage Engn, Bangalore 560012, Karnataka, India
关键词
control circuitry; gas-insulated substation (GIS); switching; transient currents; transient fields; transient voltages;
D O I
10.1109/TPWRD.2007.901292
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The transient fields generated during switching operations in gas-insulated substations (GIS) can have rise times in the order of a few nanoseconds. Transient fields, which are developed internally to the gas-insulated modules, leak into the external environment through discontinuities and interfere with nearby electronics. Depending on the configuration of the GIS and the observation point, amplitudes of the electric and magnetic fields could be of the order of a few tens of kilovolts per meter and a few hundreds of amps per meter, respectively. These transient fields, in turn, induce voltages in the control cables and secondary circuit of the instrument transformers, which result in malfunctioning of the primary equipment. In this paper, induced transient voltages in the control circuitry and their frequency spectra have been calculated due to the transient fields, leaking out from the gas-to-air bushing and the gas-insulated bus section of a 245-kV-rated GIS, during switching operations. The effect of the length of control circuit, type of grounding of the cable sheath (both-end/one-end), characteristics of the transient fields, type of secondary circuit (i.e., current transformer/potential transformer) and LC loading of the control circuitry on the induced voltages have been analyzed and reported.
引用
收藏
页码:1505 / 1513
页数:9
相关论文
共 9 条
[1]   RADIO INTERFERENCE AND TRANSIENT FIELD FROM GAS-INSULATED SUBSTATIONS [J].
HARVEY, SM ;
WONG, PS ;
BALMA, PM ;
MISAKIAN, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (01) :357-364
[2]   VERY FAST TRANSIENTS IN GIS [J].
MEPPELINK, J ;
DIEDERICH, K ;
FESER, K ;
PFAFF, W .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (01) :223-233
[3]   Frequency characteristics of very fast transient currents in a 245-kV GIS [J].
Rao, AM ;
Thomas, MJ ;
Singh, BP .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (04) :2450-2457
[4]  
RAO MM, IN PRESS IEEE T ELEC
[5]  
Rao MM, 2004, COMPUTATION MEASUREM, pB3
[6]  
SMITH AA, 1987, COUPLING EXTERNAL EL
[7]   INDUCED TRANSIENTS IN SUBSTATION CABLES - MEASUREMENTS AND MODELS [J].
THOMAS, DE ;
WIGGINS, CM ;
SALAS, TM ;
NICKEL, FS ;
WRIGHT, SE .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (04) :1861-1868
[8]   SWITCHING TRANSIENT FIELDS IN SUBSTATIONS [J].
WIGGINS, CM ;
WRIGHT, SE .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (02) :591-600
[9]   TRANSIENT ELECTROMAGNETIC-INTERFERENCE IN SUBSTATIONS [J].
WIGGINS, CM ;
THOMAS, DE ;
NICKEL, FS ;
WRIGHT, SE ;
SALAS, TM .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (04) :1869-1884