Robust Multi-Period OPF With Storage and Renewables

被引:135
作者
Jabr, Rabih A. [1 ]
Karaki, Sami [1 ]
Korbane, Joe Akl [1 ]
机构
[1] Amer Univ Beirut, Dept Elect & Comp Engn, Beirut 11072020, Lebanon
关键词
Energy storage; integer linear programming; optimal power flow; optimization methods; OPTIMAL POWER-FLOW; UNIT COMMITMENT; WIND POWER; PARTICIPATION FACTORS; ECONOMIC-DISPATCH; GENERATION; OPERATION; ALGORITHM; SYSTEMS; LOAD;
D O I
10.1109/TPWRS.2014.2365835
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Renewable energy sources and energy storage systems present specific challenges to the traditional optimal power flow (OPF) paradigm. First, storage devices require the OPF to model charge/discharge dynamics and the supply of generated power at a later time. Second, renewable energy sources necessitate that the OPF solution accounts for the control of conventional power generators in response to errors of renewable power forecast, which are significantly larger than the traditional load forecast errors. This paper presents a sparse formulation and solution for the affinely adjustable robust counterpart (AARC) of the multi-period OPF problem. The AARC aims at operating a storage portfolio via receding horizon control; it computes the optimal base-point conventional generation and storage schedule for the forecasted load and renewable generation, together with the constrained participation factors that dictate how conventional generation and storage will adjust to maintain feasible operation whenever the renewables deviate from their forecast. The approach is demonstrated on standard IEEE networks dispatched over a 24-h horizon with interval forecasted wind power, and the feasibility of operation under interval uncertainty is validated via Monte Carlo analysis. The computational performance of the proposed approach is compared with a conventional implementation of the AARC that employs successive constraint enforcement.
引用
收藏
页码:2790 / 2799
页数:10
相关论文
共 40 条
[1]   SECURITY CONSTRAINED ECONOMIC DISPATCH WITH PARTICIPATION FACTORS BASED ON WORST CASE BUS LOAD VARIATIONS [J].
ADLER, RB ;
FISCHL, R .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (02) :347-356
[2]  
[Anonymous], 2013, Power generation, operation, and control
[3]  
[Anonymous], CHANCE CONSTRAINED O
[4]  
[Anonymous], OPTIMA
[5]  
[Anonymous], 2012, P 2012 IEEE POW EN S, DOI DOI 10.1109/PESGM.2012.6344684
[6]   REAL-TIME OPTIMAL POWER FLOW IN AUTOMATIC-GENERATION CONTROL [J].
BACHER, R ;
VANMEETEREN, HP .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1988, 3 (04) :1518-1529
[7]   Adjustable robust solutions of uncertain linear programs [J].
Ben-Tal, A ;
Goryashko, A ;
Guslitzer, E ;
Nemirovski, A .
MATHEMATICAL PROGRAMMING, 2004, 99 (02) :351-376
[8]   Adaptive Robust Optimization for the Security Constrained Unit Commitment Problem [J].
Bertsimas, Dimitris ;
Litvinov, Eugene ;
Sun, Xu Andy ;
Zhao, Jinye ;
Zheng, Tongxin .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (01) :52-63
[9]  
Carr S., 2012, P INT C REN EN POW Q, P1
[10]  
Castillo A, 2013, IEEE DECIS CONTR P, P429, DOI 10.1109/CDC.2013.6759919