Development of modular air containment system: Thermal performance optimization of row-based cooling for high-density data centers

被引:29
作者
Cho, Jinkyun [1 ]
Kim, Youngmo [2 ]
机构
[1] Hanbat Natl Univ, Dept Bldg & Plant Engn, Daejeon 34158, South Korea
[2] VIVANS Co Ltd, Business Div, Seoul 06108, South Korea
基金
新加坡国家研究基金会;
关键词
Data center; Row-based cooling; Air containment system; Thermal performance; Cooling provisioning; CFD simulation; AISLE CONTAINMENT; MANAGEMENT; METRICS;
D O I
10.1016/j.energy.2021.120838
中图分类号
O414.1 [热力学];
学科分类号
摘要
Modular air containment (MAC) prototype was developed for optimal row-based cooling system for high-density data centers. The main purpose of this study is to evaluate the thermal performance , compare the cooling provisioning of different configurations of row-based cooling system to find the optimum placement of in-row CRAC units. Techno-optimal estimations were performed considering different in-row CRAC placements and aisle layouts. A matrix combination was analyzed based on total 2592 cases that can be implemented. By the whole optimization process of in-row cooler placement, we can achieve the best solution with the statically balanced cooling provisioning with a margin of error of 0.2%. The cooled air from in-row CRAC units was supplied with almost no heat loss in the air distribution paths to each server. Numerical simulations confirmed that the cold-hot-cold (C-H-C) aisle layout can improve the minimum 9% of heat balance for the provisioned CRACs compared to the hot-cold-hot (H-C -H) aisle layout. Temperature distributions, air streamlines and net cooling usages showed that the C-H -C aisle layout has better thermal performance and cooling provisioning especially for the row-based cooling. The C-H-C aisle layout is more proper than the H-C-H aisle layout for achieving the desired cooling efficiency.& nbsp; (c) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:18
相关论文
共 40 条
[1]   Thermal management and performance enhancement of data centers architectures using aligned/staggered in-row cooling arrangements [J].
Abbas, A. M. ;
Huzayyin, A. S. ;
Mouneer, T. A. ;
Nada, S. A. .
CASE STUDIES IN THERMAL ENGINEERING, 2021, 24 (24)
[2]   Innovative Approaches of Experimentally Guided CFD Modeling for Data Centers [J].
Alissa, H. A. ;
Nemati, K. ;
Sammakia, B. ;
Ghose, K. ;
Seymour, M. ;
Schmidt, R. .
2015 31ST ANNUAL SEMICONDUCTOR THERMAL MEASUREMENT, MODELING & MANAGEMENT SYMPOSIUM (SEMI-THERM), 2015, :176-184
[3]  
[Anonymous], 2015, ASHRAE T.C. 9.9
[4]  
Beaty DL, 2013, ASHRAE J, V55, P72
[5]   Cooling systems in data centers: state of art and emerging technologies [J].
Capozzoli, Alfonso ;
Primiceri, Giulio .
SUSTAINABILITY IN ENERGY AND BUILDINGS: PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE SEB-15, 2015, 83 :484-493
[6]   Thermal metrics for data centers: a critical review [J].
Capozzoli, Alfonso ;
Serale, Gianluca ;
Liuzzo, Lucia ;
Chinnici, Marta .
6TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, 2014, 62 :391-400
[7]   A Novel Methodology to Improve Cooling Efficiency at Data Centers [J].
Cheong, Kang Hao ;
Tang, Kenneth Jian Wei ;
Koh, Jin Ming ;
Yu, Simon Ching Man ;
Acharya, U. Rajendra ;
Xie, Neng-Gang .
IEEE ACCESS, 2019, 7 :153799-153809
[8]  
Cho J., Korea Patent, Patent No. 1022046410000
[9]   A Comparative CFD Study of Two Air Distribution Systems with Hot Aisle Containment in High-Density Data Centers [J].
Cho, Jinkyun ;
Woo, Jesang ;
Park, Beungyong ;
Lim, Taesub .
ENERGIES, 2020, 13 (22)
[10]   Development and experimental study of an independent row-based cooling system for improving thermal performance of a data center [J].
Cho, Jinkyun ;
Woo, Jesang .
APPLIED THERMAL ENGINEERING, 2020, 169