Assessing the energy and indoor-PM2.5-exposure impacts of control strategies for residential energy recovery ventilators

被引:15
作者
Zhong, Xuyang [1 ]
Wu, Wei [1 ]
Ridley, Ian A. [1 ]
机构
[1] City Univ Hong Kong, Sch Energy & Environm, Hong Kong, Peoples R China
来源
JOURNAL OF BUILDING ENGINEERING | 2020年 / 29卷
关键词
Building simulation; Energy consumption; Indoor PM2.5 exposure; Energy recovery ventilator; Control strategy; BUILDINGS; AIR; PM2.5; PERFORMANCE; EXPOSURE; SIMULATION; HVAC; PARTICLES; DWELLINGS; POLLUTION;
D O I
10.1016/j.jobe.2019.101137
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The energy recovery ventilator (ERV) is a type of mechanical equipment that provides ventilation into the building while reducing the energy required to condition the ventilation air. A computer modelling approach was used to assess energy consumption (the energy used to run the air-conditioning and ERV) and indoor PM2.5 exposure concentrations from both indoor and outdoor sources in Hong Kong high-rise residential flats under various ERV control strategies. Three varying inputs, including ventilation mode (energy-exchange, bypass or a hybrid of both), filter efficiency and ventilation rate, were used to develop different ERV control strategies. The estimated energy consumption and indoor PM2.5 exposure concentration were monetised using per-occupant cost functions, in order to allow a direct combination between the two. Results show that the ERV switching between energy-exchange and bypass modes according to outdoor weather conditions saves 43% of the annual energy cost compared with that operating in bypass mode, while the ERV operating in energy-exchange mode saves 28%. Integrating an air filter with a high PM2.5 removal efficiency into the ERV causes a reduction in the annual exposure cost with increased ventilation. By combining energy and exposure costs, this study has been able to determine the most cost-effective ventilation rate of the ERV, which costs an occupant approximately HK$ 2692 over the course of a year. Varying the ventilation rate as a function of outdoor temperatures, outdoor humidity ratios or outdoor enthalpy further reduces the combined cost compared with operating the ERV at the most cost-effective ventilation rate.
引用
收藏
页数:17
相关论文
共 53 条
  • [1] Enhancing the performance of energy recovery ventilators
    Al-Waked, Rafat
    Nasif, Mohammad Shakir
    Mostafa, Diala Bani
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2018, 171 : 196 - 210
  • [2] [Anonymous], POP CENS SUMM REP
  • [3] [Anonymous], CERT PROD DIR AIR TO
  • [4] [Anonymous], CLIM INF SERV
  • [5] [Anonymous], 2009, 160P ASHRAE
  • [6] [Anonymous], 2021, GLOB UPD 2006 WHO AI
  • [7] [Anonymous], RES TAR
  • [8] [Anonymous], 6222010 ASHRAE AM SO
  • [9] [Anonymous], 2006, CIBSE Guide A. Environmental design
  • [10] [Anonymous], GUID DES CONSTR REQ