A Comparison of Frequency-Dependent Soil Models: Electromagnetic Transient Analysis of Overhead Transmission Lines Using Modal Decomposition

被引:3
|
作者
Pascoalato, Taina Fernanda Garbelim [1 ]
de Araujo, Anderson Ricardo Justo [2 ]
Leon Colqui, Jaimis Sajid [2 ]
Kurokawa, Sergio [1 ]
Pissolato Filho, Jose [2 ]
机构
[1] Sao Paulo State Univ UNESP, Dept Elect Engn, BR-15385000 Ilha Solteira, Brazil
[2] State Univ Campinas UNICAMP, Sch Elect & Comp Engn, BR-13083852 Campinas, Brazil
基金
巴西圣保罗研究基金会;
关键词
electromagnetic analysis; lightning; multiphase overhead lines; modal decomposition; frequency-dependent soil models; TRANSFORMATION-MATRICES; WAVE-PROPAGATION; PARAMETERS; BEHAVIOR; IMPLEMENTATION; REPRESENTATION; APPROXIMATION;
D O I
10.3390/en15051687
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This article investigates the influence of four causal frequency-dependent (FD) soil models and their impact on the responses of a multiphase overhead transmission line (OHTL) with ground wires, generated by a lightning strike. The FD models proposed by Longmire-Smith (LS), Messier (M), Portela (P) and Alipio-Visacro (AV) are considered. The ground-return impedance and admittance matrices are computed with the Nagakawa approach for both frequency-constant and FD soil models. The frequency-domain modal voltages and time-domain transient voltages are assessed in this work. Modal decomposition technique is used to study the attenuation constant, propagation velocity and voltages for each propagation mode. Simulations are carried out in a frequency range of 100 Hz to 10 MHz, for OHTLs with lengths of 1 and 10 km, on soils of 700 and 4000 omega & BULL;m. Simulation results demonstrated that the Portela (P) model has resulted in more significant variation in the ground-return impedance and admittance, constant attenuation and propagation velocity in which a pronounced variation, especially at the high frequencies, is seen. On the other hand, Longmire-Smith (LS) and Messier (M) have produced similar results in both frequency and time domains. Additionally, the Alipio-Visacro (AV) model has produced intermediate responses, being the model recommended by CIGRE WG C4.33. Time-domain induced voltage waveforms obtained with the Portela (P) model has shown pronounced differences, especially at the peak values, for the high-resistive soil. This study demonstrates the importance of considering the FD soil models to assess the transient responses adequately, especially when OHTLs are on high-resistive soils.
引用
收藏
页数:31
相关论文
共 50 条
  • [1] ACCURATE MODELING OF FREQUENCY-DEPENDENT TRANSMISSION-LINES IN ELECTROMAGNETIC TRANSIENT SIMULATIONS
    MARTI, JR
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (01): : 147 - 157
  • [2] Influence of frequency-dependent characteristics of grounding and line models on transient overvoltages in overhead lines
    Alipio, Rafael
    De Miranda, Audine
    PRZEGLAD ELEKTROTECHNICZNY, 2018, 94 (02): : 1 - 4
  • [3] An Analysis of Frequency-Dependent Soil Models: Influence on the Transient Responses
    Pascoalato, Taina F. G.
    de Araujo, Anderson R. J.
    Colqui, Jaimis S. L.
    Kurokawa, Sergio
    Pissolato Filho, Jose
    2021 14TH IEEE INTERNATIONAL CONFERENCE ON INDUSTRY APPLICATIONS (INDUSCON), 2021, : 1 - 8
  • [4] The calculated methods of a frequency-dependent series impedance matrix of overhead transmission lines with a lossy ground for transient analysis problem
    Tu, VP
    Tlusty, J
    LESCOPE'03 : 2003 LARGE ENGINEERING SYSTEMS CONFERENCE ON POWER ENGINEERING, CONFERENCE PROCEEDINGS: ENERGY FOR THE FUTURE, 2003, : 159 - 163
  • [5] Analysis of multiconductor transmission lines with frequency-dependent parameters and incident electromagnetic fields
    Shinh, G
    Nakhla, N
    Achar, R
    Nakhla, M
    Erdin, I
    2005 IEEE MTT-S INTERNATIONAL MICROWAVE SYMPOSIUM, VOLS 1-4, 2005, : 1107 - 1110
  • [6] Transient Analysis of Multiphase Transmission Lines Located above Frequency-Dependent Soils
    Garbelim Pascoalato, Taina Fernanda
    Justo de Araujo, Anderson Ricardo
    Caballero, Pablo Torrez
    Leon Colqui, Jaimis Sajid
    Kurokawa, Sergio
    ENERGIES, 2021, 14 (17)
  • [7] Analysis of transient voltages and currents in short transmission lines on frequency-dependent soils
    Pascoalato, T. F. G.
    de Araujo, A. R. J.
    Kurokawa, S.
    Filho, J. Pissolato
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 194
  • [8] Transient Responses on Transmission Lines Located Above Frequency-Dependent Soil with Variable Water Content
    Pascoalato, Taina F. G.
    de Araujo, Anderson R. J.
    Kurokawa, Sergio
    Pissolato Filho, Jose
    2021 WORKSHOP ON COMMUNICATION NETWORKS AND POWER SYSTEMS (WCNPS), 2021,
  • [9] A review of methods for calculation of frequency-dependent impedance of overhead power transmission lines
    Wang, Y.-J.
    Liu, S.-J.
    Proceedings of the National Science Council, Republic of China, Part A: Physical Science and Engineering, 2001, 25 (06): : 329 - 338
  • [10] Direct phase-domain modelling of frequency-dependent overhead transmission lines
    Nguyen, HV
    Dommel, HW
    Marti, JR
    IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (03) : 1335 - 1342