Accurate fault location algorithm for shunt-compensated double circuit transmission lines using single end data

被引:19
作者
Ghorbani, Amir [1 ]
Mehrjerdi, Hasan [2 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, Abhar Branch, Abhar, Iran
[2] Qatar Univ, Dept Elect Engn, Doha, Qatar
关键词
Static Var Compensator (SVC); Fault location; Fault resistance; Double-circuit transmission lines; Negative-sequence circuit; DISTANCE PROTECTION; RELAYING SCHEME;
D O I
10.1016/j.ijepes.2019.105515
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces an accurate fault location algorithm for double-circuit transmission lines compensated by Static Var Compensator (SVC). The proposed algorithm is based on the negative-sequence circuit of the transmission system and it depends only on the current data available from one end of the line. Since only magnitudes of current signals are required, there is no need for data synchronization. The proposed technique uses the COMTRADE fault files available from digital distance relays and it can effectively locate the all types of unbalanced faults, regardless the high fault resistance, effect of mutual coupling and SVC current injection information. As one formula can be used for all types of fault, classification of fault types and phase selection are not required. The shunt capacitances of the line are considered by utilizing the distributed parameters model of the transmission lines. The proposed algorithm is rigorously investigated for various fault scenarios in SVC compensated transmission system. The simulation cases in the MATLAB environment verifies that the proposed scheme has excellent performance. Test results are compared with a conventional fault location technique to illustrate the accuracy of the proposed algorithm.
引用
收藏
页数:9
相关论文
共 22 条
[1]   Synchrophasor-based backup distance protection of multi-terminal transmission lines [J].
Al-Emadi, Nasser A. ;
Ghorbani, Amir ;
Mehrjerdi, Hasan .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (13) :3304-3313
[2]  
[Anonymous], 1999, C371111999 IEEE
[3]  
Blackburn J.L., 2007, PROTECTIVE RELAYING, V3rd
[4]   Ground distance relay compensation based on fault resistance calculation [J].
Eissa, M. M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (04) :1830-1835
[5]   Accurate fault location algorithm for transmission lines in the presence of shunt-connected flexible AC transmission system devices [J].
Ghazizadeh-Ahsaee, M. ;
Sadeh, J. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2012, 6 (03) :247-255
[6]   Negative-Sequence Network Based Fault Location Scheme for Double-Circuit Multi-Terminal Transmission Lines [J].
Ghorbani, Amir ;
Mehrjerdi, Hasan .
IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (03) :1109-1117
[7]   Impact of SVC on the protection of transmission lines [J].
Ghorbani, Amir ;
Khederzadeh, Mojtaba ;
Mozafari, Babak .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 42 (01) :702-709
[8]   Universal pilot relaying scheme for series and shunt-compensated lines [J].
Gupta, Om Hari ;
Tripathy, Manoj .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (04) :799-806
[9]   An Innovative Pilot Relaying Scheme for Shunt-Compensated Line [J].
Gupta, Om Hari ;
Tripathy, Manoj .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (03) :1439-1448
[10]  
Hingorani Narain., 2000, Understanding FACTS: Concepts and Technology of Flexible AC Transmission Systems, P1, DOI DOI 10.1109/9780470546802.CH1