Lightning Overvoltage Investigation due to a Backflashover Event in Transmission Lines: a realist modeling proposal

被引:0
|
作者
Rodrigues, Andre Roger [1 ]
Boaventura, Wallace do Couto [2 ]
Guimaraes, Geraldo Caixeta [3 ]
Caixeta, Daniel Araujo [3 ]
Ribeiro Chaves, Marcelo Lynce [3 ]
Tamashiro, Marcio Augusto [4 ]
机构
[1] IFMG Fed Inst Minas Gerais, Formiga, Brazil
[2] UFMG Fed Univ Minas Gerais, Belo Horizonte, MG, Brazil
[3] UFU Fed Univ Uberlandia, Uberlandia, MG, Brazil
[4] IFTO Fed Inst Tocantins, Palmas, Brazil
来源
2015 INTERNATIONAL SYMPOSIUM ON LIGHTNING PROTECTION (XIII SIPDA) | 2015年
关键词
backflashover; insulation coordination; leader progression model; lightning performance; transmission lines;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a study about the lightning performance of transmission lines using advanced electromagnetic models to perform a realistic representation of the first stroke current. Based on the measurement data obtained at the Morro do Cachimbo/MG Station, it was possible to synthesize first stroke current waveforms with single-an double-peak in a realistic way. In addition, the investigation involves an analysis with a model implemented in ATP-Models to reproduce the first stroke current recommended by CIGRE methodology. The breakdown process was represented through a Leader Progression Model able to represent accurately the physical process established along the perimeter of the insulator strings, during a backflashover event. The results allowed an investigation of the waveforms and amplitudes of the resulting overvoltages across the insulators. The computational modeling developed permits to identify the amplitude of the overvoltage that produces the backflashover and the instant of time that the breakdown occurs.
引用
收藏
页码:231 / 238
页数:8
相关论文
共 50 条
  • [21] Assessment of Overvoltage and Insulation Coordination in Mixed HVDC Transmission Lines Exposed to Lightning Strikes
    Asif, Mansoor
    Lee, Ho-Yun
    Park, Kyu-Hoon
    Shakeel, Ayesha
    Lee, Bang-Wook
    ENERGIES, 2019, 12 (21)
  • [22] Lightning performance of transmission lines: Assessing the quality of traditional methodologies to determine backflashover rate of transmission lines taking as reference results provided by an advanced approach
    Silveira, Fernando H.
    Visacro, Silverio
    Souza, Ronaldo E.
    ELECTRIC POWER SYSTEMS RESEARCH, 2017, 153 : 60 - 65
  • [23] Backflashover rate of quadruple-circuit transmission lines due to first and subsequent return strokes
    Jiang, Anfeng
    Fu, Zhengcai
    Huang, Bo
    Wang, Guoli
    Li, Ruihai
    ELECTRIC POWER SYSTEMS RESEARCH, 2016, 139 : 47 - 51
  • [24] The Evaluation of Transmission Line Modeling on Lightning Performance Considering Surger Arresters: Impact in the Energy and Backflashover Rates
    Colqui, Jaimis S. L.
    Moura, Rodolfo A. R.
    Schroeder, Marco Aurelio O.
    Pissolato Filho, Jose
    JOURNAL OF CONTROL AUTOMATION AND ELECTRICAL SYSTEMS, 2024, 35 (04) : 731 - 741
  • [26] Modeling and Insulation Performance Analysis of Composite Transmission Line Tower Under Lightning Overvoltage
    Huangfu, Youpeng
    Wang, Shuhong
    Wang, Guolin
    Xu, Weijie
    Zhang, Haijun
    IEEE TRANSACTIONS ON MAGNETICS, 2015, 51 (03)
  • [27] Monte-Carlo-based simulation and investigation of 230 kV transmission lines outage due to lightning
    Karami, Ehsan
    Khalilinia, Ahmad
    Bali, Afshar
    Rouzbehi, Kumars
    HIGH VOLTAGE, 2020, 5 (01) : 83 - 91
  • [28] Identification of Lightning Stroke Due to Shielding Failure and Backflashover for Ultra-High-Speed Transmission-Line Protection
    Morales, John
    Orduna, Eduardo A.
    Rehtanz, Christian
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (04) : 2008 - 2017
  • [29] Lightning Impulse Corona Characteristic of 1000-kV UHV Transmission Lines and Its Influences on Lightning Overvoltage Analysis Results
    Yang, Pengcheng
    Chen, Shuiming
    He, Jinliang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) : 2518 - 2525
  • [30] Tower modeling for lightning analysis of. overhead transmission lines
    Martinez, JA
    Castro-Aranda, F