Experimental assessment of a pilot scale hybrid cooling system for water consumption reduction in CSP plants

被引:8
作者
Palenzuela, Patricia [1 ]
Roca, Lidia [1 ]
Asfand, Faisal [2 ]
Patchigolla, Kumar [3 ]
机构
[1] CIEMAT Plataforma Solar Almeria CIESOL, Ctra Senes S-N, Almeria 04200, Spain
[2] Univ Huddersfield, Sch Comp & Engn, Huddersfield HD1 3DH, W Yorkshire, England
[3] Cranfield Univ, Ctr Thermal Energy & Mat, Sch Water Energy & Environm, Cranfield MK43 0AL, Beds, England
关键词
Hybrid cooling; Pilot plant; Water consumption saving; Experimental characterization; Optimal operating strategies; POWER-PLANT; TOWER; PERFORMANCE; ABATEMENT; PLUME; CYCLE; DRY;
D O I
10.1016/j.energy.2021.122948
中图分类号
O414.1 [热力学];
学科分类号
摘要
The new challenge of the European Commission is to limit water consumption in Concentrating Solar Power (CSP) plants, especially significant in the cooling process. Hybrid cooling systems are presented as a potential solution to achieve water consumption reduction since they also avoid a high penalty of efficiency loss in the power block. In this work, a hybrid cooling pilot plant installed at Plataforma Solar de Almeria is evaluated experimentally. The system has been tested under different ambient and operating conditions to analyze their influence on the water and electricity consumption. The results reveal that significant water savings were achieved in comparison with the conventional only-wet configuration. Concretely, a maximum water consumption saving of 67% was found at high ambient temperatures (between 25 and 30 degrees C) and for a thermal load of 80% when a hybrid configuration was used. The optimal operating strategies that achieve a tradeoff between low water and electricity consumption have been identified by two efficiency indexes: the specific electricity and water consumption. The parallel configuration was the optimal one in most of the cases. At high ambient temperatures and 80% thermal load, the electricity and water consumptions of this configuration were 0.033 kW(e)/kWth and 0.071 L/kWth, respectively. (C) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:12
相关论文
共 26 条
  • [1] Thermodynamic Performance and Water Consumption of Hybrid Cooling System Configurations for Concentrated Solar Power Plants
    Asfand, Faisal
    Palenzuela, Patricia
    Roca, Lidia
    Caron, Adele
    Lemarie, Charles-Andre
    Gillard, Jon
    Turner, Peter
    Patchigolla, Kumar
    [J]. SUSTAINABILITY, 2020, 12 (11)
  • [2] Comparative evaluation of hybrid (dry/wet) cooling tower performance
    Asvapoositkul, Wanchai
    Kuansathan, Mantheerapol
    [J]. APPLIED THERMAL ENGINEERING, 2014, 71 (01) : 83 - 93
  • [3] Exergetic comparison of two different cooling technologies for the power cycle of a thermal power plant
    Blanco-Marigorta, Ana M.
    Victoria Sanchez-Henriquez, M.
    Pena-Quintana, Juan A.
    [J]. ENERGY, 2011, 36 (04) : 1966 - 1972
  • [4] Experimental characterization of a multi-effect distillation system coupled to a flat plate solar collector field: Empirical correlations
    Chorak, Aicha
    Palenzuela, Patricia
    Alarcon-Padilla, Diego-Cesar
    Ben Abdellah, Abdellatif
    [J]. APPLIED THERMAL ENGINEERING, 2017, 120 : 298 - 313
  • [5] Water consumption in solar parabolic trough plants: review and analysis of the southern Spain case
    Colmenar-Santos, Antonio
    Borge-Diez, David
    Perez Molina, Clara
    Castro-Gil, Manuel
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 34 : 565 - 577
  • [6] Environmental impact from wet plumes in combined-cycle power plants
    Corti, A
    Carnevale, E
    [J]. APPLIED THERMAL ENGINEERING, 1998, 18 (11) : 1049 - 1057
  • [7] Costs of reducing water use of concentrating solar power to sustainable levels: Scenarios for North Africa
    Damerau, Kerstin
    Williges, Keith
    Patt, Anthony G.
    Gauche, Paul
    [J]. ENERGY POLICY, 2011, 39 (07) : 4391 - 4398
  • [8] Retrofit of a wet cooling tower in order to reduce water and fan power consumption using a wet/dry approach
    Dehaghani, Shahed Taghian
    Ahmadikia, Hossein
    [J]. APPLIED THERMAL ENGINEERING, 2017, 125 : 1002 - 1014
  • [9] Feasibility study for reduce water evaporative loss in a power plant cooling tower by using air to Air heat exchanger with auxiliary Fan
    Deziani, M.
    Rahmani, Kh.
    Roudaki, S. J. Mirrezaei
    Kordloo, M.
    [J]. DESALINATION, 2017, 406 : 119 - 124
  • [10] Comparative study on the performance of natural draft dry, pre-cooled and wet cooling towers
    He, Suoying
    Gurgenci, Hal
    Guan, Zhiqiang
    Hooman, Kamel
    Zou, Zheng
    Sun, Fengzhong
    [J]. APPLIED THERMAL ENGINEERING, 2016, 99 : 103 - 113